for
tSlaveDeadTime
is 0.1sec because both master and slave should not send the
breaker closing command at the same time. The slave should take the duration of the
breaker closing time of the master into consideration before sending the breaker
closing command. A setting
tWaitForMaster
sets a maximum wait time for the
WAIT
input to reset. If the wait time expires, the reclosing cycle of the slave is inhibited. If
auto reclosing of the first breaker is unsuccessful, the
UNSUCCL
output connected to
the
INHIBIT
input of the slave unit interrupts the auto reclosing sequence of the latter.
The signals can be cross-connected to allow simple changing of the
priority by just setting the High and the Low priorities without
changing the configuration. The input
52a
for each circuit breaker is
important in multi-breaker arrangements to ensure that the circuit
breaker was closed at the beginning of the cycle. If the High priority
circuit breaker is not closed the High priority moves to the low priority
circuit breaker.
Section 14
1MRK 511 401-UUS A
Control
344
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...