Measurement function application for a 380kV OHL
SEMOD54481-12 v11
Single line diagram for this application is given in figure
:
380kV Busbar
380kV OHL
P
Q
800/5 A
ANSI09000039-1-en.vsd
380kV 120V
/
3 3
kV
IED
ANSI09000039 V1 EN-US
Figure 207:
Single line diagram for 380kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as indicated
in figure
it is necessary to do the following:
1. Set correctly CT and VT data and phase angle reference channel
PhaseAngleRef
“Setting of the phase reference channel”
) using PCM600 for analog
input channels
2. Connect, in PCM600, measurement function to three-phase CT and VT inputs
3. Set under General settings parameters for the Measurement function:
•
general settings as shown in table
.
•
level supervision of active power as shown in table
.
•
calibration parameters as shown in table
.
Section 17
1MRK 511 401-UUS A
Monitoring
516
Bay control REC670 2.2 ANSI
Application manual