The residual current, out on the line, is calculated at an operational case with minimal
ground-fault current. The requirement that the whole line shall be covered by step 2
can be formulated according to equation
step2
0
I
0.7 3I (at remote busbar)
³
×
EQUATION1202 V4 EN-US
(Equation 42)
To assure selectivity the current setting must be chosen so that step 2 does not operate
at step 2 for faults on the next line from the remote substation. Consider a fault as
shown in Figure
One phase-ground-fault
67N
50/51N
50/51N
67N
0
3I
0x
3I
ANSI05000155_2_en.vsd
ANSI05000155 V2 EN-US
Figure 75:
Step 2, selectivity calculation
A second criterion for step 2 is according to equation
.
1
1
0
step2
step1
0
3I
I
.2
I
3I
³
×
×
EQUATION1203 V4 EN-US
(Equation 43)
where:
I
step1
is the current setting for step 1 on the faulted line.
Step 3
M15282-164 v6
This step has directional function and a time delay slightly larger than step 2, often 0.8
s. Step 3 shall enable selective trip of ground faults having higher fault resistance to
ground, compared to step 2. The requirement on step 3 is selectivity to other ground-
fault protections in the network. One criterion for setting is shown in Figure
Section 8
1MRK 511 401-UUS A
Current protection
182
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...