The minimum operating voltage has to be calculated (all loops) and the IED function is
set higher than the highest achieved value (setting
TripPickup
). As the loop resistance
is the value to the connection point from each CT, it is advisable to do all the CT core
summations in the switchgear to have shortest possible loops. This will give lower
setting values and also a better balanced scheme. The connection in to the control room
can then be from the most central bay.
For an internal fault, all involved CTs will try to feed current through the measuring
branch. Depending on the size of current transformer, relatively high voltages will be
developed across the series resistor. Note that very high peak voltages can appear. To
prevent the risk of flashover in the circuit, a voltage limiter must be included. The
voltage limiter is a voltage dependent resistor (Metrosil).
The external unit with stabilizing resistor has a value of either 6800 ohms or 1800
ohms (depending on ordered alternative) with a sliding link to allow adjustment to the
required value. Select a suitable value of the resistor based on the VR voltage
calculated. A higher resistance value will give a higher sensitivity and a lower value a
lower sensitivity of the relay.
The function has a recommended operating current range 40 mA to 1.0A for 1 A inputs
and 200 mA to 5A for 5A inputs. This, together with the selected and set value, is used
to calculate the required value of current at the set
TripPickup
and
R series
values.
The CT inputs used for 1Ph High impedance differential protection
HZPDIF (87) function, shall be set to have ratio 1:1. So the parameters
CT
secx
and
CT
primx
of the relevant channel x of TRM and/or AIM shall
be set equal to 1 A by PST in PCM600; The parameter
CTStarPointx
may be set to
ToObject
.
The tables
,
below show, the operating currents for different settings of operating
voltages and selected resistances. Adjust as required based on tables
in between as required for the application.
Minimum ohms can be difficult to adjust due to the small value
compared to the total value.
Normally the voltage can be increased to higher values than the calculated minimum
TripPickup
with a minor change of total operating values as long as this is done by
adjusting the resistor to a higher value. Check the sensitivity calculation below for
reference.
1MRK 511 401-UUS A
Section 7
Differential protection
Bay control REC670 2.2 ANSI
131
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...