14.2.2.7
Maximum number of reclosing shots
M12391-120 v7
The maximum number of auto reclosing shots in an auto reclosing cycle is selected by
the setting
NoOfShots
. A maximum of five shots can be done. The type of auto
reclosing used at the first auto reclosing shot is set by the setting
ARMode
. The first
alternative is three-phase auto reclosing. The other alternatives include some single-
phase or two-phase auto reclosing. Usually there is no two-pole tripping arranged, and
then there will be no two-phase auto reclosing.
The decision for single- and three-phase trip is also made in the tripping logic
(SMPTTRC) function block where the setting
3 phase
,
1ph/3Ph
(or
1ph/2ph/3Ph
) is
selected.
14.2.2.8
ARMode = 3ph, (normal setting for a three-phase shot)
M12391-124 v5
Three-phase auto reclosing, one to five shots according to the
NoOfShots
setting. The
prepare three-pole trip PREP3P output is always set (high). A trip operation is made as
a three-pole trip for all type of faults. The auto reclosing is as a three-phase auto
reclosing as in mode 1/2/3ph described below. All signals, blockings, inhibits, timers,
requirements and so on, are the same as in the example described below.
14.2.2.9
ARMode = 1/2/3ph
M12391-127 v8
Single-phase, two-phase or three-phase auto reclosing first shot, followed by 3-phase
auto reclosing shots, if selected. Here, the auto recloser is assumed to be "On" and
"Ready". The circuit breaker is closed and the operation gear ready (operating energy
stored).
START
input (or
STARTHS
) is received and sealed-in. The
READY
output is
reset (set to false).
ACTIVE
output is set.
•
If
TR2P
and
TR3P
inputs are low (i.e. single-phase trip): The timer for single-
phase auto reclosing dead time is started and the
1PT1
output (single-phase
reclosing in progress) is activated. It can be used to suppress pole disagreement
and earth-fault protection trip during the single-phase dead time interval..
•
If
TR2P
input is high and
TR3P
input is low (i.e. two-phase trip): The timer for
two-phase auto reclosing dead time is started and the
2PT1
output (two-phase
reclosing in progress) is activated.
•
If
TR3P
input is high (i.e. three-phase trip): The timer for three-phase auto
reclosing dead time,
t1 3Ph
or
t1 3PhHS
, is started depending on if
START
or
STARTHS
input has been activated and
3PT1
output (three-phase reclosing shot 1
in progress) is set..
While any of the auto reclosing dead time timers are running, the
INPROGR
output is
activated. When the dead time runs out, the respective internal signal is transmitted to
the output module for further checks and to issue a breaker closing command.
Section 14
1MRK 511 401-UUS A
Control
330
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...