If the busbar is divided by bus-section circuit breakers, the signals from the bus-section
coupler bay (A1A2_BS), rather than the bus-section disconnector bay (A1A2_DC),
must be used. For B1B2_BS, corresponding signals from busbar B are used. The same
type of module (A1A2_BS) is used for different busbars, that is, for both bus-section
circuit breakers A1A2_BS and B1B2_BS.
Signal
S1S2CLTR
A bus-section coupler connection exists between bus sections 1 and 2.
VPS1S2TR
The switch status of bus-section coupler BS is valid.
EXDU_BS
No transmission error from the bay containing the above information.
For a bus-coupler bay in section 1, these conditions are valid:
AND
BC_12_CL
VP_BC_12
EXDU_BC
en04000485_ansi.vsd
AND
AND
DCCLTR (A1A2)
DCCLTR (B1B2)
BC12CLTR (sect.2)
VPDCTR (A1A2)
VPDCTR (B1B2)
VPBC12TR (sect.2)
EXDU_DC (A1A2)
EXDU_DC (B1B2)
EXDU_BC (sect.2)
ANSI04000485 V1 EN-US
Figure 139:
Signals to a bus-coupler bay in section 1 from a bus-coupler bay in
another section
For a bus-coupler bay in section 2, the same conditions as above are valid by changing
section 1 to section 2 and vice versa.
14.4.3.5
Configuration setting
M13553-107 v4
If there is no bypass busbar and therefore no 289 and 789 disconnectors, then the
interlocking for 289 and 789 is not used. The states for 289, 789, 7189G are set to open
by setting the appropriate module inputs as follows. In the functional block diagram, 0
and 1 are designated 0=FALSE and 1=TRUE:
•
289_OP = 1
•
289_CL = 0
•
789_OP = 1
•
789_CL = 0
Section 14
1MRK 511 401-UUS A
Control
382
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...