Trip value rec
Fault locator
Sequential of
events
Event recorder
Indications
Disturbance
recorder
Disturbance Report
Binary signals
Analog signals
DRPRDRE
FL
ANSI09000336-2-en.vsdx
AxRADR
BxRBDR
ANSI09000336 V2 EN-US
Figure 211:
Disturbance report functions and related function blocks
For Disturbance report function there are a number of settings which also influences
the sub-functions.
Three LED indications placed above the LCD screen makes it possible to get quick
status information about the IED.
Green LED:
Steady light
In Service
Flashing light
Internal failure
Dark
No power supply
Yellow LED:
Steady light
Triggered on binary signal N with SetLEDx = Start (or Start and
Trip)
Flashing light
The IED is in test mode
Table continues on next page
Section 17
1MRK 511 401-UUS A
Monitoring
534
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...