Protection
Function
Protection
Function
Tele-
Protection
Equipment
Tele-
Protection
Equipment
Tele-
communication
System
CS from the
protection
function, operate
and reset time
CS initiation to
the
communication
system, operate
and reset time
CS propagation,
propagation
CR selection and
decision, operate
and reset time
CR to the
protection
function, operate
and reset time
Time
Fault
occurs
Protection
pick-up CS initiation
CR to
teleprot.
eq.
CR to
prot.
func
Fault current
reversal
Sending
protection
reset
CS to
communication
drop
CR
reception
drop
CR to
prot.
func
drop
Minimum setting of
tDelay
IEC05000536-2-en.vsd
IEC05000536 V2 EN-US
Figure 198:
Time sequence of signaling at current reversal
15.5.3.2
Weak-end infeed
M13933-12 v6
The weak-end infeed can be set by setting the parameter
WEI
to
Off
,
Echo
or
Echo &
Trip
. Operating zero sequence voltage when parameter
WEI
is set to
Echo & Trip
is set
with 3V0PU.
The zero sequence voltage for a fault at the remote line end and appropriate fault
resistance is calculated.
To avoid unwanted trip from the weak-end infeed logic (if spurious signals should
occur), set the operate value of the broken delta voltage level detector (3V0) higher
than the maximum false network frequency residual voltage that can occur during
normal service conditions. The recommended minimum setting is two times the false
zero-sequence voltage during normal service conditions.
Section 15
1MRK 511 401-UUS A
Scheme communication
484
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...