tPCrvx
,
tACrvx
,
tBCrvx
,
tCCrvx
: Parameters for programmable inverse time
characteristic curve. The time characteristic equation is according to equation
:
[ ]
p
A
t s
B TD
i
C
ipickup
=
+
×
-
æ
ö
ç
÷
ç
÷
ç
÷
æ
ö
ç
÷
ç
÷
è
ø
è
ø
EQUATION1722 V1 EN-US
(Equation 45)
Further description can be found in the Technical reference manual (TRM).
tPRCrvx
,
tTRCrvx
,
tCRCrvx
: Parameters for customer creation of inverse reset time
characteristic curve. Further description can be found in the Technical Reference
Manual.
8.5.3.2
Common settings for all steps
GUID-A00A942B-E760-42EE-8FEB-F723426783F3 v1
x
means step 1, 2, 3 and 4.
AngleRCA
: Relay characteristic angle given in degrees. This angle is defined as shown
in figure
. The angle is defined positive when the residual current lags the reference
voltage (Vpol = -)
1MRK 511 401-UUS A
Section 8
Current protection
Bay control REC670 2.2 ANSI
189
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...