Setting
Short Description
Selected value
MarchAmbTmp
Set the March month average ambient
temperature for the calculation of top oil
temperature when ambient temperature
sensor failure/absence
30° C
AprilAmbTmp
Set the April month average ambient
temperature for the calculation of top oil
temperature when ambient temperature
sensor failure/absence
30° C
MayAmbTmp
Set the May month average ambient
temperature for the calculation of top oil
temperature when ambient temperature
sensor failure/absence
30° C
JuneAmbTmp
Set the June month average ambient
temperature for the calculation of top oil
temperature when ambient temperature
sensor failure/absence
30° C
JulyAmbTmp
Set the July month average ambient
temperature for the calculation of top oil
temperature when ambient temperature
sensor failure/absence
30° C
AugAmbTmp
Set the August month average ambient
temperature for the calculation of top oil
temperature when ambient temperature
sensor failure/absence
30° C
SepAmbTmp
Set the September month average
ambient temperature for the calculation of
top oil temperature when ambient
temperature sensor failure/absence
30° C
OctAmbTmp
Set the October month average ambient
temperature for the calculation of top oil
temperature when ambient temperature
sensor failure/absence
30° C
NovAmbTmp
Set the November month average
ambient temperature for the calculation of
top oil temperature when ambient
temperature sensor failure/absence
30° C
DecAmbTmp
Set the December month average
ambient temperature for the calculation of
top oil temperature when ambient
temperature sensor failure/absence
30° C
HPTmpRiseW1
Set the hot spot temperature rise of
winding 1 for the calculation of hot spot to
top oil temperature gradient
65° C
HPTmpRiseW2
Set the hot spot temperature rise of
winding 2 for the calculation of hot spot to
top oil temperature gradient
65° C
HPTmpRiseW3
Set the hot spot temperature rise of
winding 3 for the calculation of hot spot to
top oil temperature gradient
65° C
Table continues on next page
1MRK 511 401-UUS A
Section 17
Monitoring
Bay control REC670 2.2 ANSI
563
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...