Application
SEMOD55350-5 v8
Generic communication function for Single Point Value (SPGAPC) function is used to
send one single logical output to other systems or equipment in the substation.
SP16GAPC can be used to send up to 16 single point values from the application
functions running in the same cycle time. SPGAPC has one visible input and
SPGAPC16 has 16 visible inputs that should be connected in the ACT tool.
Setting guidelines
SEMOD55376-5 v5
There are no settings available for the user for SPGAPC.
Generic communication function for Measured Value MVGAPC
SEMOD55402-1 v3
Application
SEMOD55872-5 v10
Generic communication function for measured values (MVGAPC) function is used to
send the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an
analog value and to permit measurement supervision on that value.
Setting guidelines
SEMOD55424-5 v5
The settings available for Generic communication function for Measured Value
(MVGAPC) function allows the user to choose a deadband and a zero deadband for the
monitored signal. Values within the zero deadband are considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal, low
and low-low ranges of the measured value. The actual range of the measured value is
shown on the range output of MVGAPC function block. When a Measured value
expander block (RANGE_XP) is connected to the range output, the logical outputs of
the RANGE_XP are changed accordingly.
20.2.3.2
Receiving data
GUID-CAE4B020-7131-49BF-BA29-3EEE0EFEA2B8 v1
The GOOSE data must be received at function blocks. There are different GOOSE
receiving function blocks depending on the type of the received data. Refer to the
Engineering manual for more information about how to configure GOOSE.
Function block type
Data Type
GOOSEBINRCV
16 single point
GOOSEINTLKRCV
2 single points
16 double points
GOOSEDPRCV
Double point
GOOSEINTRCV
Integer
GOOSEMVRCV
Analog value
Table continues on next page
Section 20
1MRK 511 401-UUS A
Station communication
580
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...