Function block type
Data Type
GOOSESPRCV
Single point
GOOSEVCTRRCV
VCTR signals parallel mode
GOOSEXLNRCV
Switch status
Application
GUID-808177B7-02CA-40DF-B41B-8B580E38478B v1
The GOOSE receive function blocks are used to receive subscribed data from the
GOOSE protocol. The validity of the data value is exposed as outputs of the function
block as well as the validity of the communication. It is recommended to use these
outputs to ensure that only valid data is handled on the subscriber IED. An example
could be to control the external reservation before operating on a bay. In the figure
below, the GOOSESPRCV is used to receive the status of the bay reservation. The
validity of the received data is used in additional logic to guarantee that the value has
good quality before operation on that bay.
GOOSESPRCV
Block Spout
DataValid
CommValid
Test
AND
AND
Input1 out
Input2 Noput
Input3
Input4
Input1 out
Input2 Noput
Input3
Input4
Ext_Res_OK_To_Operate
IEC16000082=1=en.vsd
IEC16000082 V1 EN-US
Figure 224:
GOOSESPRCV and AND function blocks - checking the validity of the
received data
1MRK 511 401-UUS A
Section 20
Station communication
Bay control REC670 2.2 ANSI
581
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...