SpChAlmTime
: Time delay for spring charging time alarm.
tDGasPresAlm
: Time delay for gas pressure alarm.
tDGasPresLO
: Time delay for gas pressure lockout.
DirCoef
: Directional coefficient for circuit breaker life calculation.
RatedOperCurr
: Rated operating current of the circuit breaker.
RatedFltCurr
: Rated fault current of the circuit breaker.
OperNoRated
: Number of operations possible at rated current.
OperNoFault
: Number of operations possible at rated fault current.
CBLifeAlmLevel
: Alarm level for circuit breaker remaining life.
AccSelCal
: Selection between the method of calculation of accumulated energy.
OperTimeDelay
: Time delay between change of status of trip output and start of main
contact separation.
17.5
Event function EVENT
IP14590-1 v2
17.5.1
Identification
SEMOD167950-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Event function
EVENT
S00946 V1 EN-US
-
17.5.2
Application
M12805-6 v11
When using a Substation Automation system with LON or SPA communication, time-
tagged events can be sent at change or cyclically from the IED to the station level.
These events are created from any available signal in the IED that is connected to the
Event function (EVENT). The EVENT function block is used for remote
communication.
Analog, integer and double indication values are also transferred through the EVENT
function.
Section 17
1MRK 511 401-UUS A
Monitoring
530
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...