Operate
Angle1(2)
Power1(2)
P
Q
en06000441.vsd
IEC06000441 V1 EN-US
Figure 87:
Underpower mode
The setting
Power1(2)
gives the power component pick up value in the
Angle1(2)
direction. The setting is given in p.u. of the generator rated power, see equation
Minimum recommended setting is 0.2% of S
N
when metering class CT inputs into the
IED are used.
N
S
3 VBase IBase
=
×
×
EQUATION2047 V1 EN-US
(Equation 73)
The setting
Angle1(2)
gives the characteristic angle giving maximum sensitivity of the
power protection function. The setting is given in degrees. For active power the set
angle should be 0° or 180°. 0° should be used for generator low forward active power
protection.
Section 8
1MRK 511 401-UUS A
Current protection
218
Bay control REC670 2.2 ANSI
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...