VGenZeroDb
: Minimum level of voltage in % of VBase, used as indication of zero
voltage (zero point clamping). If measured value is below
VGenZeroDb
calculated S, P,
Q and PF will be zero.
IGenZeroDb
: Minimum level of current in % of
IBase
, used as indication of zero
current (zero point clamping). If measured value is below
IGenZeroDb
calculated S, P,
Q and PF will be zero.
VMagCompY
: Magnitude compensation to calibrate voltage measurements at Y% of
Vn, where Y is equal to 5, 30 or 100.
IMagCompY
: Magnitude compensation to calibrate current measurements at Y% of In,
where Y is equal to 5, 30 or 100.
IAngCompY
: Angle compensation to calibrate angle measurements at Y% of In, where
Y is equal to 5, 30 or 100.
The following general settings can be set for the
Phase current measurement
(CMMXU).
IMagCompY
: Magnitude compensation to calibrate current measurements at Y% of In,
where Y is equal to 5, 30 or 100.
IAngCompY
: Angle compensation to calibrate angle measurements at Y% of In, where
Y is equal to 5, 30 or 100.
The following general settings can be set for the
Phase-phase voltage measurement
(VMMXU).
VMagCompY
: Amplitude compensation to calibrate voltage measurements at Y% of
Vn, where Y is equal to 5, 30 or 100.
VAngCompY
: Angle compensation to calibrate angle measurements at Y% of Vn,
where Y is equal to 5, 30 or 100.
The following general settings can be set for
all monitored quantities
included in the
functions (CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU) X in
setting names below equals S, P, Q, PF, V, I, F, IA,IB,IC, VA, VB, VCVAB, VBC,
VCA, I1, I2, 3I0, V1, V2 or 3V0.
Xmin
: Minimum value for analog signal X set directly in applicable measuring unit.
This forms the minimum limit of the range.
Xmax
: Maximum value for analog signal X. This forms the maximum limit of the
range.
XZeroDb
: Zero point clamping. A signal value less than
XZeroDb
is forced to zero.
1MRK 511 401-UUS A
Section 17
Monitoring
Bay control REC670 2.2 ANSI
513
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...