Curve name
IEC Normal Inverse
IEC Very Inverse
IEC Inverse
IEC Extremely Inverse
IEC Short Time Inverse
IEC Long Time Inverse
IEC Definite Time
User Programmable
ASEA RI
RXIDG (logarithmic)
The different characteristics are described in the Technical Reference Manual (TRM).
Pickupx
: Operation negative sequence current level for step x given in % of
IBase
.
tx
: Definite time delay for step
x
. The definite time
tx
is added to the inverse time when
inverse time characteristic is selected. Note that the value set is the time between
activation of the start and the trip outputs.
TDx
: Time multiplier for the dependent (inverse) characteristic.
IMinx
: Minimum pickup current for step x in % of
IBase
. Set
IMinx
below
Pickupx
for
every step to achieve ANSI reset characteristic according to standard. If
IMinx
is set
above
Pickupx
for any step the ANSI reset works as if current is zero when current
drops below
IMinx
.
MultPUx
: Multiplier for scaling of the current setting value. If a binary input signal
(ENMULTx) is activated the current operation level is multiplied by this setting
constant.
txMin
: Minimum operation time for inverse time characteristics. At high currents the
inverse time characteristic might give a very short operation time. By setting this
parameter the operation time of the step can never be shorter than the setting.
1MRK 511 401-UUS A
Section 8
Current protection
Bay control REC670 2.2 ANSI
187
Application manual
Summary of Contents for Relion REC670
Page 1: ...RELION 670 SERIES Bay control REC670 Version 2 2 ANSI Application manual ...
Page 2: ......
Page 26: ...20 ...
Page 42: ...36 ...
Page 96: ...90 ...
Page 274: ...268 ...
Page 292: ...286 ...
Page 298: ...292 ...
Page 308: ...302 ...
Page 470: ...464 ...
Page 514: ...508 ...
Page 608: ...602 ...
Page 646: ...640 ...
Page 656: ...650 ...
Page 657: ...651 ...