Upgrading a Single-Site System With Four Servers
185
2
Switch to the new software version by entering the following command:
vcx-switchversion 7.1.
x
c
The system displays several status messages and provides prompts that
allow you enable Adhoc Conferencing and UPS Monitoring.
3
The Adhoc Conferencing prompt appears:
In order to support "ad-hoc" conferences with more than 3
participants, the Adhoc Conference Service is used. This
service should be enabled on this server, unless another
server dedicated to Adhoc Conferencing will be used instead.
If available, a separate server typically provides greater
capacity and may be shared among sites.
Use the Adhoc service on this server? (Y/N) [Y] :
If you want this server to act as a multi-caller (up to 6 callers)
conferencing server, enter
y
. If not, enter
n
.
4
The UPS Monitoring prompt appears:
An Uninterruptible Power Supply (UPS) can be used with VCX
systems to avoid disruption due to a power outage. VCX
provides a UPS monitoring service which tracks the UPS's
status and performs a safe shutdown when the its battery is
depleted during a long power outage. To use this feature,
you must have a compatible UPS installed and configured in
accordance with the VCX documentation.
Enable UPS monitoring? [N] :
If you do not have a UPS installed and enter
n
(or press
Enter
); the
remaining UPS configuration prompts are not displayed.
If you do have a UPS installed and enter
y
and see
for information on the subsequent UPS configuration
prompts.
5
After completing the Adhoc Conferencing and UPS Monitoring prompts,
the server reboots. When the reboot process has been completed, the
system starts VCX 7.1.
x
services.
6
After the system has completed the restart process, verify that the
upgrade has occurred by entering this command:
ls -l /opt/3com/VCX
The symbolic link (VCX) should point to the new version of the VCX
software (7.1.
x
c). If the link does not point to the new version, wait a few
Summary of Contents for VCX V7000
Page 26: ...26 CHAPTER 1 VCX SYSTEM MAINTENANCE OVERVIEW ...
Page 68: ...68 CHAPTER 3 MANAGING VCX SERVERS ...
Page 78: ...78 CHAPTER 4 BACKING UP AND RESTORING A VCX CONFIGURATION ...
Page 88: ...88 CHAPTER 5 MANAGING AUTHENTICATION AND DIRECTORY SERVICE DATABASES ...
Page 100: ...100 CHAPTER 6 MANUALLY CONFIGURING MULTI MASTER REPLICATION ...
Page 140: ...140 CHAPTER 8 MANAGING UNINTERRUPTIBLE POWER SUPPLIES ...
Page 250: ...250 APPENDIX B UPGRADING VCX SERVER SOFTWARE FROM V7 1 X TO V7 1 Y ...
Page 290: ...290 APPENDIX C UPGRADING VCX SERVER SOFTWARE FROM V6 0 TO V7 0 ...
Page 328: ...328 APPENDIX D DOWNGRADING VCX SERVER SOFTWARE ...
Page 339: ...CLI Command Descriptions 339 ...