134
C
HAPTER
8: M
ANAGING
U
NINTERRUPTIBLE
P
OWER
S
UPPLIES
■
The IP address of the second UPS is 10.230.63.4.
■
The community string the second UPS will use to communicate with
the master VCX server is private.
■
The low battery threshold charge is 33%.
After the initial master VCX server configuration, you can change a
parameter value by reentering the
vcx-ups-setup
command. In the
following example, the low battery threshold charge is changed to 50%:
vcx-ups-setup --master Y --monitormultipleups Y
--upsipaddr 10.230.63.3 --community private
--upsipaddr1 10.230.63.4 --community1 private --bcharge 50
Note that you must include all the
vcx-ups-setup
command parameters
even if you are only changing a single value.
Dual UPS System – Configuring a Slave VCX Server
To enable and configure a VCX server as a slave in a multiple UPS system:
1
Log in, using the
root
account, to the VCX server you want to designate
as a slave.
2
Enter the following command:
vcx-ups-setup <configuration_parameters>
You must concatenate the following
vcx-ups-setup
command
configuration parameters (responses are shown in bold):
-- master:
N
Enter
N
(you must uppercase) to indicate that this server is not the
master.
-- monitormultipleups:
Y
Enter
Y
(you must uppercase) to indicate there are multiple UPS
devices servicing the VCX system.
-- upsserver <
IP Address of the master
>
Enter the IP address (assigned to eth0) of the VCX server acting as the
master UPS monitor. Use dotted decimal notation but do not enter
leading zeros. For example, enter 10.230.63.3,
not
010.230.063.003.
3
Repeat steps 1 and 2 for all the other VCX servers in your system that you
want to function as slaves.
Summary of Contents for VCX V7000
Page 26: ...26 CHAPTER 1 VCX SYSTEM MAINTENANCE OVERVIEW ...
Page 68: ...68 CHAPTER 3 MANAGING VCX SERVERS ...
Page 78: ...78 CHAPTER 4 BACKING UP AND RESTORING A VCX CONFIGURATION ...
Page 88: ...88 CHAPTER 5 MANAGING AUTHENTICATION AND DIRECTORY SERVICE DATABASES ...
Page 100: ...100 CHAPTER 6 MANUALLY CONFIGURING MULTI MASTER REPLICATION ...
Page 140: ...140 CHAPTER 8 MANAGING UNINTERRUPTIBLE POWER SUPPLIES ...
Page 250: ...250 APPENDIX B UPGRADING VCX SERVER SOFTWARE FROM V7 1 X TO V7 1 Y ...
Page 290: ...290 APPENDIX C UPGRADING VCX SERVER SOFTWARE FROM V6 0 TO V7 0 ...
Page 328: ...328 APPENDIX D DOWNGRADING VCX SERVER SOFTWARE ...
Page 339: ...CLI Command Descriptions 339 ...