Programming
Technical
Manual:
Smartstart
®
6000
IMI0042
rev
K
Page
28
Y11
Relay
1
Variable
Set
the
functionality
of
Relay
1.
Range:
See
table
on
page
34
Default:
Line
Ctrl
To
save
changes
To
exit
without
saving
Y20
Relay
2
Mode
Activates
Relay
2.
Range:
Enable;
Invert;
Disable
Default:
Enable
To
save
changes
To
exit
without
saving
Y21
Relay
2
Variable
Set
the
functionality
of
Relay
2.
Range:
See
table
on
page
34
Default:
Bypass
Ctrl
To
save
changes
To
exit
without
saving
NOTE:
Relay
2
must
be
configured
as
‘bypass’
for
Starters
with
internal
bypass
contactor
(6R15
‐
6R80).
Y30
Relay
3
Mode
Activates
Relay
3.
Range:
Enable;
Invert;
Disable
Default:
Enable
To
save
changes
To
exit
without
saving
Y31
Relay
3
Variable
Set
the
functionality
of
Relay
3.
Range:
See
table
on
page
34
Default:
Up
to
Speed
To
save
changes
To
exit
without
saving
Y40
Relay
4
Mode
Activates
Relay
4.
Range:
Enable;
Invert;
Disable
Default:
Enable
To
save
changes
To
exit
without
saving
Y41
Relay
4
Variable
Set
the
functionality
of
Relay
4.
Range:
See
table
on
page
34
Default:
Trip
Alarm
To
save
changes
To
exit
without
saving
Y50
An
Out
1
Mode
Activate
and
set
the
signal
type
for
Analogue
Output
1.
Range:
Disabled
;
0
‐
10v;
0
‐
5v;
0
‐
20mA;
4
‐
20mA
Default:
Disabled
To
save
changes
To
exit
without
saving
Y51
An
Out
1
Variable
Set
the
functionality
of
Analogue
Output
1.
Range:
See
table
on
page
34
Default:
Current
To
save
changes
To
exit
without
saving
Y52
An
Out
1
FS
(Full
Scale)
Set
the
full
scale
of
the
Analogue
output
signal.
Range:
50
–
500%
Default:
200%
To
save
changes
To
exit
without
saving
Example:
On
a
0
‐
120A
meter
scale
&
40Amp
Motor
FLC
Scaling
=
120/40
x
100
=
300%
Therefore,
20mA
=
300%
to
display
120A
24Hour
Timer:
The
inbuilt
24hour
timer
operates
a
relay
when
assigned.
The
relay
output
can
be
used
to
start/stop
the
soft
starter
or
used
to
control
external
devices.
Assign
either
Relay
1,
2,
3
or
4
as
‘Timer
Relay’
and
configure
the
settings
below.
Refer
to
page
14
for
wiring
into
enable/start
circuit
.
Y90
Timer
Cycles
Set
the
number
of
timer
cycles
to
operate
the
starter/motor.
Range:
0
–
120
Default:
0
To
save
changes
To
exit
without
saving
Y91
Timer
Start
Set
to
the
desired
time
for
the
cycles
to
commence
(24hour
time).
This
will
be
based
on
the
time
set
on
the
soft
starter.
Range:
Set
start
time
Default:
0
To
save
changes
To
exit
without
saving