Programming
Technical
Manual:
Smartstart
®
6000
IMI0042
rev
K
Page
36
Trip (Warning) codes & messages
A
warning
message
will
have
a
‘W’
in
place
of
the
‘T’
for
the
following
messages.
CODE/Message
Description
T00
NO
TRIP
ALM
No
fault
or
trip
has
occurred.
T01
PSU
LOW
VOLT
Control
supply
voltage
low.
Check
control
voltage.
T02
LINE
FREQ
Line
supply
frequency
out
of
range
while
motor
running.
T03
LINE
PH
FLT
3
Phase
supply
problem,
one
phase
open.
Check
L1;
L2;
L3.
T04
PHS
ROTATION
Line
Phase
sequence
in
wrong
direction
–
User
selectable.
See
P03
page
23.
T05
MTR
3/6
WIRE
Wiring
detected
different
to
motor
wiring
setting.
Check
motor
wiring.
T06
NET
T/O
Loss
of
communications
while
network
controlling
motor.
T07
CT
PHASING
Incorrect
CT
phasing
and/or
insufficient
motor
current.
Check
correct
installation
of
external
CT’s
(6
wire
only).
Check
CT
phasing
under
the
diagnostics
menu
to
check
or
help
identify
the
error.
T10
START
FAILED
Motor
did
not
start.
T11
MTR
STUCK
ON
Unexpected
motor
current
detected
while
off.
Check
wiring,
relay
configuration
and
bypass
contactor.
T13
MOTOR
LOSS
Motor
current
lost
in
all
3
phases.
Check
Motor
and
motor
wiring.
T14
BYPASS
FAULT
Bypass
Contactor
failed
to
close
or
opened
unexpectedly.
T15
BP
POLE
FLT
Bypass
Contactor
failed
to
close
or
opened
unexpectedly.
3
Phase/pole
fault.
T20
STR
OVERCURR
Starter
instantaneous
over
current
while
up
to
speed.
T21
STR
OVERTEMP
Starter
heatsink
over
temperature.
T22
STR
TEMP
FLT
Starter
heatsink
temperature
sensor
fault.
T23
STR
OVERLOAD
Starter
thermal
overload.
Motor
or
load
problem,
start
time
longer
than
normal.
Excessive
starts
per
hour.
Insufficient
start
torque
and/or
current
limit
too
low
–
check
settings.
Ambient
temperature
rating
exceeded
or
Starter
rating
exceeded.
T24
MOTOR
STALL
Motor
Stalled,
current
after
start
>300%
for
3
seconds.
Check
motor,
load
and
starter
settings.
T25
VOLT
IMBAL
Voltage
imbalance
as
per
user
setting.
See
P20
page
23.
Check
supply
T26
CURR
IMBAL
Current
imbalance
as
per
user
setting.
See
P30
page
24.
Check
supply
and
motor.
T30
MTR
OVERLOAD
Motor
thermal
overload
trip
as
per
user
setting.
See
page
20.
Incorrect
overload
class
(&
starter
rating).
Motor
or
load
problem.
Excessive
starts
per
hour
for
overload
class
selected.
Insufficient
start
torque
and/or
current
limit
too
low
–
check
settings.
T31
MTR
OVERTEMP
Motor
over
temperature
from
the
thermistor
input.
See
P02
page
23.
Check
Motor
and
Load.
CODE/Message
Description
T32
MTR
TEMP
FLT
Motor
thermistor
sensor
fault
detected.
Check
thermistor
and
wiring.
T33
MTR
OVERCURR
Over
current
trip
as
per
user
setting.
See
P50
page
25.
T34
MTR
UNDERCURR
Under
current
trip
as
per
user
setting.
See
P40
page
24.
T35
MTR
OVERTORQ
Over
torque
trip
as
per
user
setting.
See
P70
page
25
T36
MTR
UNDERTORQ
Under
torque
trip as
per
user
setting.
See
P60
page
25.
T37
D1
INPUT
ALM
Trip
initiated
from
external
source
connected
to
Digital
input
1
.
T38
D2
INPUT
ALM
Trip
initiated
from
external
source.
connected
to
Digital
input
2.
T41
ACC
OVERTIME
Acceleration
time
has
exceeded
set
time
as
per
user
setting.
See
P10
page
23.
Motor
or
load
problem,
start
time
longer
than
normal.
Insufficient
start
torque
and/or
current
limit
too
low
–
check
settings.
T42
ESO
MODE
Warning
Message
when
Essential
Services
Over
‐
ride
is
requested.
T43
A/R
LOCKOUT
Auto
Restart
Lockout
– Auto
restarts
exhausted
or
final
trip
T50
MTR
AMPS
CFG
Motor
Amps
configuration
Error
–
Check
and
adjust
motor
Amps
and/or
motor
wiring.
T60
MOTOR
FAULT
Current
not
detected
in
multiple
phases
during
breakaway
firing.
T61
T1
PHASE
FLT
Current
not
detected
in
single
phase
(T1/M1)
during
breakaway
firing.
T62
T2
PHASE
FLT
Current
not
detected
in
single
phase
(T2/M2)
during
breakaway
firing.
T63
T3
PHASE
FLT
Current
not
detected
in
single
phase
(T3/M3)
during
breakaway
firing.
T40
BRAKE
FAIL
Brake
input
indicates
External
Brake
is
ON
while
motor
Starting/Running.
.
Содержание SMARTSTART 6000
Страница 1: ...ZENER VARIDRIVE SOLUTIONS ZENER SMARTSTART 6000 Soft Starter Instruction Manual...
Страница 2: ......
Страница 49: ...Appendix B Application Diagrams Technical Manual Smartstart 6000 IMI0042 rev K Page 46 General Purpose...
Страница 51: ...Appendix B Application Diagrams Technical Manual Smartstart 6000 IMI0042 rev K Page 48 Irrigation Pump...