Programming
Technical
Manual:
Smartstart
®
6000
IMI0042
rev
K
Page
32
N11
RS485
Speed
(RS485
only)
Adjust
to
the
required
baud
rate.
Range:
4800,9600,19k2,38k4
Default:
19k2
To
save
changes
To
exit
without
saving
N12
RS485
Format
(RS485
only)
Select
the
correct
protocol
format.
Range:
8o1,
8n1,
8n2,
8e1
Default:
8e1
To
save
changes
To
exit
without
saving
N20
IP
Address
(Ethernet
Only)
Enter
the
IP
address
in
format
shown
N21
IP
Address
1
(Ethernet
Only)
Range:
0
‐
255
Default:
0
To
save
changes
To
exit
without
saving
N22
IP
Address
2
(Ethernet
Only)
Range:
0
‐
255
Default:
0
To
save
changes
To
exit
without
saving
N23
IP
Address
3
(Ethernet
Only)
Range:
0
‐
255
Default:
0
To
save
changes
To
exit
without
saving
N24
IP
Address
4
(Ethernet
Only)
Range:
0
‐
255
Default:
0
To
save
changes
To
exit
without
saving
N25
IP
Mask
Bits
(Ethernet
Only)
Range:
/2
‐
/30
Default:
/24
To
save
changes
To
exit
without
saving
To
clear/reset
any
of
the
following
a
confirmation
code
is
required:
1
Reset
Trip
2
ClrTrip
Log
3
Clr
Mtr
OL
4
Clr
Counters
5
Clr
Meters
6
Copy
Par1
to
Par2
7
Restore
Defaults
The
Confirmation
Code
is:
1470
This
menu
provides
indication
of
inputs
and
wiring
checks.
Digital
In:
0
=
No
control
signal
present
1
=
Control
signal
present
Thermistor
In:
Displays
thermistor
resistance
in
Kohms.
The
trip
resistance
is
3000
Ohms
and
a
short
circuit
is
detected
when
<20
Ohms.
Ambient
temperature
is
also
displayed
when
a
data
logger
option
is
fitted.
Relay
Status:
Displays
relay
status
of
internal
relays
for
Fan,
Bypass
and
Programmable
Relays
1,
2,
3
and
4.
Chk
Motor
Wiring:
The
detected
motor
wiring
is
displayed.
On
power
up
(3phase,
without
attempting
a
start)
an
incorrect
motor
wiring
will
be
displayed.
This
is
particularly
useful
for
ensuring
the
correct
6
wire
configuration.
Example:
‘Correct
Mtr
3
wire
‘
Chk
CT1/CT2
Displays
detected
CT
connection.
Example:
‘Correct
+L1
/
+L3’
Setup Menu
10 Commands
Setup Menu
11 Starter Diag
Digital EN D1 D2
Inputs 0 0 0
Enable
Input
Digital
1
Input
Digital
2
Input
N20 IP Address
000 . 000 . 000. 000
Содержание SMARTSTART 6000
Страница 1: ...ZENER VARIDRIVE SOLUTIONS ZENER SMARTSTART 6000 Soft Starter Instruction Manual...
Страница 2: ......
Страница 49: ...Appendix B Application Diagrams Technical Manual Smartstart 6000 IMI0042 rev K Page 46 General Purpose...
Страница 51: ...Appendix B Application Diagrams Technical Manual Smartstart 6000 IMI0042 rev K Page 48 Irrigation Pump...