Installation
‐
Mechanical
Technical
Manual:
Smartstart
®
6000
IMI0042
rev
K
Page
4
Mechanical Installation
The
Smartstart
®
6000
should
be
installed
by
qualified
electrical
personnel
only.
The
following
should
be
considered
when
installing.
Mount
in
a
vibration
free
environment.
Mount
vertically
and
away
from
heat
radiating
sources.
Do
not
mount
in
direct
sunlight
or
on
hot
surfaces.
Mount
in
a
suitable
enclosure
for
the
environment
in
which
it
is
to
operate,
the
total
heat
dissipation
must
be
considered.
Do
not
drill
holes
into
the
Smartstart
®
6000
enclosure.
Do
not
allow
metal
shavings
or
any
other
conductive
material
to
enter
the
enclosure
or
damage
may
result.
Clearances
for
airflow:
Models:
6R15/30/60/80
Only:
Below
illustrates
the
clearances
to
allow
access
to
Ports
if
fitted;
i)
Remote
Console
(RJ
Connection)
ii)
SD
Card
Slot
iii)
Ethernet
Port
Heat Dissipation
The
Smartstart
®
6000
is
cooled
by
temperature
controlled
internal
fans.
Installing
a
bypass
contactor
will
reduce
the
heat
dissipated
and
the
ventilation
required.
Soft
Starters
generally
dissipate
approximately
4.5watts
per
Amp
when
operated
without
a
bypass
contactor.
The
heat
dissipated
can
be
calculated
by;
Continuous
Duty:
P
=
(FLC
x
4.5)
Bypass
Duty:
P
=
(FLC
x
SC
x
4.5
x
t
x
N)
/
3600
Where;
P
=
Power
dissipated
in
Watts
FLC
=
Nameplate
FLC
of
Motor
SC
=
Average
starting
current
expressed
per
unit
of
FLC
t
=
Starting
time
N
=
Number
of
starts
per
hour
When
installing
the
Smartstart
®
6000
in
an
enclosure
or
switch
board
it
is
necessary
to
consider
the
heat
dissipated
and
then
the
ventilation
required.
The
following
formula’s
will
assist
in
determining
whether
ventilation
is
required
and
how
much.
Ventilated
Enclosure:
V
=
(3.1
x
P)
/
T
Where;
V
=
Airflow
required
in
m3/hour
P
=
Power
dissipated
in
Watts
T
=
Temperature
differential
in
°C
(inside
–
outside)
Non
Ventilated
Enclosure:
A
=
P
/
(
T
x
k)
Where;
A
=
Exposed
surface
area
of
cabinet
(m2)
P
=
Power
dissipated
in
Watts
T
=
Temperature
differential
(°C)
(inside
–
outside)
k
=
Heat
transmission
constant
(5
for
Painted
metal)
> 75mm
> 75mm
> 20mm
> 75mm
> 75mm