Control
Wiring
Technical
Manual:
Smartstart
®
6000
IMI0042
rev
K
Page
14
Default/Standard Control:
1.
Standard
Power
‐
up
Start
(no
Soft
Stop)
2.
Standard
Run/Stop
using
enable
input
(Soft
Start/Soft
Stop
or
Coast)
C20
Decel
Ramp
:
0.0
for
coast
:
Adjust
for
soft
stop
(>0)
If
enable
is
left
on,
power
‐
up
start
will
be
supported
3.
Standard
Run/stop
using
built
‐
in
24hour
cycle
timer
Start/stop
by
internal
timer.
See
page
28
for
details
Alternative configuration available:
1.
3
wire
Start/Stop
A53
Start
Logic
:
‘edge
sensed’
X10
Dig
In
1
:
Enabled
X11
Dig
In
1
Variable
:
Start
(latching)
X11
Dig
In
1
Delay
:
0.0sec
Use
enable
or
DIG
in2
for
stop:
X20
Dig
In
2
:
Invert
X21
Dig
In
2
Variable
:
Stop
X22
Dig
In
2
Delay
:
0.0sec
C20
Decel
Ramp
:
0.0
for
coast
:
Adjust
for
soft
stop
(>0)
2.
Delayed
Soft
Start
and/or
Soft
Stop
Multiple
pump
control
systems
or
prestart
warning
A
X10
Dig
In
1
:
Enabled
X11
Dig
In
1
Variable
:
Start
(latching)
X11
Dig
In
1
Delay
:
Adjust
to
suit
(0
‐
300seconds)
X20
Dig
In
2
:
Invert
X21
Dig
In
2
Variable
:
Stop
X22
Dig
In
2
Delay
:
Adjust
to
suit
(0
‐
300seconds)
(Adjust
Accel
and
Decel
to
suit
application)
Control
Supply
24VDC
12/13
ENABLE
14
DIGIn
1
15
DIGIn
2
16
RUN
/
STOP
Control
Supply
24VDC
12/13
ENABLE
14
DIGIn
1
15
DIGIn
2
16
Control
Supply
24VDC
12/13
ENABLE
14
DIG
In
1
15
DIG
In
2
16
START
STOP
Control
Supply
24VDC
12/13
ENABLE
14
DIG
In
1
15
DIG
In
2
16
START
STOP
Control
Supply
24VDC
12/13
ENABLE
14
Relay
3
or
4
‘TIMER
RELAY’