Programming
Technical
Manual:
Smartstart
®
6000
IMI0042
rev
K
Page
23
C22
Release
Torq:
The
Smartstart
®
6000
will
decelerate
the
motor
at
the
‘decel
time’
rate
until
the
torque
reaches
the
release
torque
value
entered.
This
is
entered
as
a
percentage
of
nominal
Torque
(FLT).
Range:
0
to
100%
Default:
20%
To
save
changes
To
exit
without
saving
In
pump
applications
the
deceleration
provided
by
the
Smartstart
®
6000
will
reduce
problems
with
water
hammer
with
greater
control
of
the
motor
torque
&
speed.
The
Smartstart
®
6000
has
advanced
settings
to
customise
the
control
of
the
motor
during
acceleration
and
deceleration.
Refer
to
Menu
‘Advanced
Controls’
on
page
29
for
more
details.
C30
Accel
Ramp
2
:
(2
nd
Parameter
Enabled)
C31
Accel
Time
2:
Accel
Ramp
for
2
nd
parameter
operation
when
enabled
and
activated
used
digital
input
1
or
2.
Range:
1
to
60
seconds
Default:
10
s
To
save
changes
To
exit
without
saving
C32
Start
Torque
2:
The
initial
torque
for
2
nd
parameter
operation.
Range:
0%
to
200%
Default:
30%
To
save
changes
To
exit
without
saving
C33
Final
Torque
2:
(torque
control
only)
This
sets
the
torque
provided
at
the
end
of
the
acceleration
period.
Range:
15
to
200%
Default:
100%
To
save
changes
To
exit
without
saving
C40
Decel
Ramp:
(2
nd
Parameter
Enabled)
C21
Decel
Time:
The
time
taken
to
decelerate
the
motor
from
100%
to
0%
V
or
FLT
for
2
nd
parameter
operation
Range:
0
to
120
seconds
Default:
0
s
To
save
changes
To
exit
without
saving
C42
Release
Torq:
Release
Torque
for
2
nd
parameter
operation
.
Range:
0
to
100%
Default:
20%
To
save
changes
To
exit
without
saving
Some
protection
may
be
set
for
trip
or
warn.
A
‘Trip’
will
cause
the
soft
starter
to
stop
without
a
soft
stop,
based
on
the
parameters
configured.
A
Warning
is
based
on
the
configuration
of
A43
warning
level
or
A44
Warning
delay
and
will
not
cause
the
soft
starter
to
trip
or
motor
to
stop.
P01
Mtr
Overload:
The
Smartstart
®
6000
continuously
monitors
the
motor
current
(even
in
bypass)
and
calculates
the
temperature
rise
of
the
motor.
The
tripping
curves
are
based
on
the
protection
classes
as
defined
by
IEC60947
‐
4
‐
2.
Refer
to
page
39
for
more
details
on
overload
class
curves.
Select
the
overload
protection
class
suitable
for
the
motor
&
load
combination.
This
protection
is
type
R1,
thus
will
not
reset
the
thermal
capacity
when
power
is
removed
or
motor
is
stopped.
This
prevents
the
motor
from
restarting
if
the
motor
is
too
hot.
Range:
2;10a;10;15;20;25;30;disabled
Default:
10
To
save
changes
To
exit
without
saving
The
overload
setting
must
be
selected
according
to
the
motor
manufacturers
recommendations.
P02
Mtr
OverTemp:
Provides
overload
protection
of
the
motor
by
monitoring
the
actual
motor
temperature.
A
thermistor
(PTC
Type
only)
or
NC
switch
can
be
connected
directly
to
terminals
20
and
21.
This
will
operate
in
conjunction
with
P02
Mtr
Therm
OL.
i.
Trip
resistance:
3000
Ω
ii.
Reset:
1650
Ω
iii.
Thermistor
Fault:
<20
Ω
Range:
Thermistor
(PTC
only);
NC
switch;
disabled
Default:
Disabled
To
save
changes
To
exit
without
saving
Setup Menu