Programming
Technical
Manual:
Smartstart
®
6000
IMI0042
rev
K
Page
29
Y92
Timer
Run
Set
to
the
desired
run
time
for
the
Soft
Starter/Motor.
Range:
00.00
to
20.00
hh:mm
Default:
0
To
save
changes
To
exit
without
saving
Y93
Timer
Wait
Set
to
the
desired
off
time
for
the
Soft
Starter/Motor
before
the
next
run
cycle
commences.
Range:
00.00
to
20.00
hh:mm
Default:
0
To
save
changes
To
exit
without
saving
A10
Kick
Start
Set
to
provide
a
kick
during
starting.
This
provides
an
adjustable
torque
boost
to
the
motor
when
a
start
is
initiated.
This
will
also
result
in
a
higher
start
current
during
the
kick
duration.
When
a
kick
time
of
0.0
seconds
is
selected
‘Disabled’
will
be
displayed.
To
enter
submenu
to
modify
To
exit
sub
menu
A11
Kick
Time
Set
to
the
time
of
the
kick
Range:
0.0
–
2.0
seconds
Default:
0.0
(Disabled)
To
save
changes
To
exit
without
saving
A12
Kick
Level
Set
the
level
of
kick
as
a
percentage
%
of
Locked
Rotor
Current.
Range:
50
–
100%
Default:
70%
To
save
changes
To
exit
without
saving
A20
Accel
Method
The
acceleration
method
allows
adjustment
of
the
aceleration
profile
and
acceleration
control.
This
provides
advanced
control
of
the
motor
during
the
ramp
time
to
better
match
the
type
of
load
or
application.
See
Appendix
A
on
Page
44
for
more
details.
To enter submenu to modify
To exit sub menu
A21
Accel
Profile
Select
the
type
of
acceleration
profile
to
match
the
type
of
load
or
application.
Example:
Pump/Fan
=
Squared
Range:
Linear,
Squared
Default:
Squared
To
save
changes
To
exit
without
saving
A22
Accel
Control
Select
the
type
of
Acceleration
control
to
suit
the
load
or
application.
Torque
Control
will
provide
greater
control
of
motor
acceleration.
Range:
Torque;
Voltage
Default:
Torque
To
save
changes
To
exit
without
saving
A30
Decel
Method
The
deceleration
method
allows
adjustment
of
the
deceleration
profile
and
acceleration
control
of
the
Soft
Starter.
This
provides
advanced
control
of
the
motor
during
the
ramp
down
time
to
better
match
the
type
of
load
or
application.
This
is
especially
useful
in
resolving
water
hammer
related
problems.
Setup Menu
8 Advanced
Kick
Time
Kick
Level
A10 Kick Start
0.2s 70%
Accel
Profile
Accel
Control
A20 Accel Method
Squared
Torque
Decel
Profile
Decel
Control
A30 Decel Method
Linear
Torque