Appendix A
Indicative parameters for different load types
Technical
Manual:
Smartstart
®
6000
IMI0042
rev
K
Page
45
1.
Pump
(3
wire/Bypass
with
No
Soft
Stop)
Factory
defaults
are
intended
for
general
pumping/fan
application
with
no
Soft
Stop.
Enter
motor
parameters
as
per
motor
nameplate.
2.
Submersible
Pump
(3
wire/Bypass
with
No
Soft
Stop)
Factory
defaults
are
intended
for
general
pumping
application
with
no
Soft
Stop.
The
acceleration
time
needs
to
be
reduced
to
3secs
or
as
per
pump/motor
manufacturers
recommendations.
Enter
motor
parameters
as
per
motor
nameplate.
Ref
Page
Parameter
Setting
(factory
Default)
C11
22
Accel
time
3sec
(10s)
M01
21
Motor
Amps
‘Nameplate
Motor
FLC’
M02
21
Motor
Volts
‘Nameplate
Motor
Volts’
M03
21
Motor
PF
‘Nameplate
Motor
PF’
3.
Pump
:(3
wire/Bypass
with
Soft
Stop)
Factory
defaults
are
intended
for
general
pumping
application
with
no
Soft
Stop.
Enter
motor
parameters
as
per
motor
nameplate.
Adjust
the
‘Release
Torque’
and
‘Decel
time’
to
achieve
the
required
soft
stop.
Ref
Page
Parameter
Setting
(factory
Default)
C21
22
Decel
time
*15sec
(0s)
C22
22
Release
Torque
*2%
(2%)
M01
21
Motor
Amps
‘Nameplate
Motor
FLC’
M02
21
Motor
Volts
‘Nameplate
Motor
Volts’
M03
21
Motor
PF
‘Nameplate
Motor
PF’
4.
Fan
:(3
wire/Bypass)
Factory
defaults
are
intended
for
general
pumping
application
which
is
similar
to
that
required
for
a
fan.
However,
the
Accel
time
may
need
to
be
increased
to
allow
for
longer
ramp
times
of
high
inertia
fans.
The
Motor
Overload
Class
may
also
need
to
be
increased
with
the
extended
ramp
of
high
inertia
fans.
Enter
motor
parameters
as
per
motor
nameplate.
Ref
Page
Parameter
Setting
(factory
Default)
C11
22
Accel
time
15+
(10s)
P01
23
Motor
Overload
Class
10
/Class
20
(10)
M01
21
Motor
Amps
‘Nameplate
Motor
FLC’
M02
21
Motor
Volts
‘Nameplate
Motor
Volts’
M03
21
Motor
PF
‘Nameplate
Motor
PF’
5.
Conveyor:
(3
wire/Bypass)
Factory
defaults
are
preset
for
a
variable
torque
load.
The
Torque
settings
will
need
to
be
adjusted
for
a
constant
torque
type
load.
Enter
motor
parameters
as
per
motor
nameplate.
Ref
Page
Parameter
Setting
(factory
Default)
C12
22
Start
Torque
80%
(30%)
C13
22
Final
Torque
150%
(130%)
A21
29
Accel
profile
Linear
(Squared)
P01
23
Motor
Overload
Class
20
(10)
M01
21
Motor
Amps
‘Nameplate
Motor
FLC’
M02
21
Motor
Volts
‘Nameplate
Motor
Volts’
M03
21
Motor
PF
‘Nameplate
Motor
PF’
6.
Compressor:
(3
wire/Bypass)
Factory
defaults
are
preset
for
a
variable
torque
load.
The
Torque
settings
will
need
to
be
adjusted
for
a
constant
torque
type
load.
Enter
motor
parameters
as
per
motor
nameplate
.
Ref
Page
Parameter
Setting
(factory
Default)
C12
22
Start
Torque
60%
(30%)
C13
222
Final
Torque
130%
(130%)
A21
29
Accel
profile
Linear
(Squared)
P01
23
Motor
Overload
Class
20
(10)
M01
21
Motor
Amps
‘Nameplate
Motor
FLC’
M02
21
Motor
Volts
‘Nameplate
Motor
Volts’
M03
21
Motor
PF
‘Nameplate
Motor
PF’
7.
Suggested
Protection
Settings
Below
are
suggested
settings
to
provide
additional
protection
of
the
motor
and
load.
These
are
general
settings
and
should
be
further
tuned
to
suit
the
application
and
load
conditions.
Ref
Page
Parameter
Setting
(factory
Default)
P01
23
Motor
Overload
Class
10a/10/20
(10)
P02
23
Motor
O/Temp
Thermistor
(Disabled)
P03
23
Phase
Rotation
1
‐
2
‐
3
(Disabled)
P10
23
Accel
O/Time
Trip
/
5s
(Disabled)
P20
24
Volt
Imbal.
Trip
/
25%
/
5s
(Default)
P30
24
Current
Imbal.
Trip
/
25%
/
10s
(Default)
P41
24
Under
Current
Trip
/
50%
/
10s
(Disabled)
P70
25
Over
Torque
Trip
/
110%
/
10
s
(Disabled)