Programming
Technical
Manual:
Smartstart
®
6000
IMI0042
rev
K
Page
21
D05
(Flash)
Warnings/Alarms:
General
inclusion
of
warning
alarms
to
be
‘flashed
over’
the
current
dashboard
screen.
Refer
to
table
4
(p35
&
36)
for
alarm
message
explanation.
Selection:
All
Alarms;
Disabled;
Trips
only;
Flt
Warnings;
Major
Warnings
Default:
All
Alarms
To
save
changes
To
exit
without
saving
D06
Alm
over
Bar:
The
default
screen
will
display
when
a
trip
has
occurred,
with
details
of
the
type
of
trip
in
the
trip
log.
The
Smartstart
®
6000
may
be
configured
to
display
the
trip
or
alarm
warning
on
the
default
screen
(over
the
bar
graph).
The
highest
priority
active
alarm
is
displayed
in
place
of
the
bar
graph
(only
when
the
motor
is
off).
Refer
to
table
5
(p35
&
36)
for
alarm
message
explanation.
Selection:
All
Alarms;
Disabled;
Trips
only;
Flt
Warnings;
Major
Warnings
Default:
All
Alarms
To
save
changes
To
exit
without
saving
Level/Option:
Description:
1/Trips
Only
Only
displays
‘trip’
Alarms
(T##).
Incl.
Tripped,
AR
&
Lockout
alerts.
2/Flt
Warnings:
Include
fault
warning
alarms:
(W02,22,15,14,11,05,07,32,08,06)
3/Major
Warnings:
Include
major
warning
alarms:
(W02,04,13,23,21,20,31,30,24,25,26)
4/All
Warnings:
Include
remaining
(minor)
alarms
(W37,38,41,33,35,34,36)
5/All
Alarms:
Include
interlock
warning
alarms
(see
‘I’
message/alarms
on
page
36)
D10
Date:
Set
the
date
of
real
time
clock
Adjust
the
value
of
time
To
save
changes
To
exit
without
saving
D20
Time:
Set
the
time
of
real
time
clock
Adjust
the
value
of
time
To
save
changes
To
exit
without
saving
M01
Motor
Amps:
Adjust
to
the
value
of
motor
full
load
current
(FLC)
indicated
on
the
motor
rating
plate,
even
if
connected
in
6
wire
(inside
delta).
Range:
40%
of
Nom.
unit
rating
to
max.
rating
Default:
Nom.
rating
of
unit
To
save
changes
To
exit
without
saving
[‘Nom.
unit
rating’
=
3wire,
bypass,
light
duty]
M02
Motor
Volts:
Adjust
the
value
to
the
motor
nameplate
voltage.
Range:
199
–
481V
[480
‐
1160V]
Default:
415V
[1000V]
To
save
changes
To
exit
without
saving
M03
Motor
PF:
Adjust
to
the
value
to
the
motor
Power
Factor
as
indicated
on
the
motor
rating
plate.
Range:
0.60
–
0.98
Default:
0.90
To
save
changes
To
exit
without
saving
M04
Motor
Wiring:
(excl.
6R15
‐
6R80)
Select
the
wiring
configuration
of
the
soft
starter.
Range:
3
Wire;
Std
6
Wire;
Alt
6
Wire
Default:
3
Wire
To
save
changes
To
exit
without
saving
C01
Run
Mode:
Set
to
the
configuration
of
the
Smartstart
6000.
Range:
Bypass;
Continuous
Default:
Bypass
To
save
changes
To
exit
without
saving
Where
an
internal
bypass
contactor
is
fitted
this
must
be
set
to
bypass.
If
set
to
continuous
the
internal
bypass
contactor
will
not
energise.
Setup Menu
2 Motor
Setup Menu