Installation
‐
Power
Terminals
(up
to
80Amp)
Technical
Manual:
Smartstart
®
6000
IMI0042
rev
K
Page
7
3 Wire with integral Bypass
Only
Models;
6R015B2
&
6R005B2
6R030B2
6R060B2
6R080B2
Power
Terminations
Model:
Max
cable
size
Tightening
Torque
6R005B2
6
mm
2
1.5
–
1.8
Nm
6R015B2
6
mm
2
1.5
–
1.8
Nm
6R030B2
6
mm
2
1.5
–
1.8
Nm
6R060B2
35mm
2
3.2
–
3.7
Nm
6R080B2
35mm
2
3.2
–
3.7
Nm
Earth
M6
stud
‐
Semiconductor
Fuse
kit
(Optional)
Refer
to
Page
43
for
selection.
Semiconductor
Fuse
Replacement
Refer
to
Page
43
for
replacement
fuses.
Refer to page 13-14
For Control Wiring
(1)
Optional
Fast
Acting
Semiconductor
Fuses
selected
to
suit
the
SCR
devices
used.
(2)
Line
Contactor
controlled
by
the
Soft
Starter.
(see
Control
wiring
on
Page
13
&
14
and
application
drawings
on
Page
46
‐
48)
(3)
Models
6R5
to
6R80
include
an
integral
Bypass
Contactor.
With
these
models
an
external
bypass
contactor
is
not
required.