Specification
Technical
Manual:
Smartstart
®
6000
IMI0042
rev
K
Page
38
Input
Voltage:
6R
series:
220
to
460Vac
6R15
‐
80:
380Vac
to
415Vac
6V
series:
600
to
1000V
(+10%)
Input
Frequency:
50
/
60Hz
+/
‐
3Hz,
Auto
detecting
Control
Supply:
24Vdc
(+15%,
‐
15%)
24VDC
Power
Supply
(min.
requirements):
Power
Supply
O/P:
24VDC
Regulated
Peak
power
requirements:
6R15
‐
30:
1.5
Amps
(36W)
6R60
‐
80:
2
Amps
(48W)
6R100–220/6V90:
3.0Amps
(72W)
6R300–880:
4.0
Amps
(96W)
6V200
‐
400:
4.0
Amps
(96W)
These
ratings
allow
for
peak
current
requirements
of
internal
fans
AC
Control
Supply
Options
Available:
240VAC:
All
Models
18VAC:
All
Models
415VAC
Self
Powered
6R15/30/60/80
Only
Configurations:
i)
3
wire
&
6
wire
ii)
Bypass
or
Continuous
6R15
to
6R80
have
integral
Bypass
Contactor.
Duty
:
Light
Duty:
300%
for
15
secs;
10start/hr
350%
for
10secs;
10start/hr
Standard
Duty:
300%
for
30secs;
10start/hr
400%
for
10
secs;
10start/hr
Severe
Duty:
450
for
20
secs;
5start/hr
300%
for
60
secs;
5start/hr
SCR
PIV:
Minimum
1400V
(6R
series)
Minimum
3600V
(6V
series)
SCR
configuration:
Full
‐
wave
Dv/dt
suppression:
RC
snubber
networks
Over
Voltage:
MOV
Rated
Insulation:
2Kv
(6R
series)
EMC
Class
A
(to
AS61800
–
C
‐
tick)
Current
Feedback
Current
transformer
in
circuit
at
all
times.
Torque
controlled
Ramp
or
voltage
ramp,
with
current
limit
override
Standards
Compliance
AS31800
C
‐
tick;
AS3947.4.2,
IEC60947
‐
4
‐
2
Environment:
Enclosure
protection:
IP00
–
IP20
Operating
Temp.
0
to
55°C
(derate
by
1%
/
°C
>40°C)
Cooling:
Temperature
controlled
forced
ventilated
Maximum
Altitude:
1000m
without
derating
Operating
position:
Vertical
Pollution:
Degree
3
conforming
to
IEC947
‐
4
‐
2
Inputs:
Digital
Inputs
:
24Vdc
Logic
Function:
2x
Programmable
inputs
1x
Enable
Input
Thermistor:
Thermistor
or
NC
switch
PTC
type,
Trip
Resistance
3000Ohms,
<20ohms
detected
as
Short
Circuit.
Outputs:
Digital
Output:
4
Programmable
Relays
Contact
Rating:
5A
250Vac;
5A
30VDC
resistive
Analogue
Output:
1x
Programmable
Output
Signal:
0
‐
10V,
0
‐
5V,
4
‐
20mA
Communications:
Modbus
RS485
(Standard)
Ethernet
(Modbus)
Option
Protection:
Motor
Overload
Adjustable;
Class
10,
10A,
20,
25,
30
type
R1,
total
memory
function
SCR
Over
temp.
Heat
sink
temperature
SCR
protection:
Current
&
thermal
modelling
Under
Current
Adjustable
level
and
trip
time
Over
Current
Adjustable
level
and
trip
time
Under
Torque:
Adjustable
level
and
trip
time
Over
Torque:
Adjustable
level
and
trip
time
Motor
Stalled
300%
for
3
seconds
(run
mode
only)
Current
limit
Adjustable
Starter
Overload
Current
&
thermal
modelling
O/P
Short
Circuit
Semiconductor
fuses
(optional)
Voltage
imbalance
Input
voltage
imbalance
Current
Imbalance
Input
&
output
current
imbalance
Bypass
failure
No
bypass
after
ramp
time
or
during
run
mode
SCR
fault
Open
or
Short
circuit
SCR
Acc
over
time
Accel
time
exceeds
set
time
Phase
reversal
Phase
rotation
inhibit
Motor
Loss
Motor
or
output
open
cct
CT
fault
Fault
with
CT’s
Line
Freq/Phase
Problem
with
supply
Network
Timeout
Network
Fault
Remote
Input
Forced
trip
from
external
source
Human
Interface
Module
(HIM):
Type:
Local
or
remote
mountable
(IP66)
Display:
Backlit
LCD
(Blue)
,
English
Menu:
Coded
&
English
Menu
Protected:
Selectable
user
access
code
Cable
type:
Ribbon
or
Cat
‐
5
Essential
Services
Over
‐
ride
(ESO):
Selectable
Digital
input
with
24Vdc
logic.
Battery:
Type:
CR1220
Содержание SMARTSTART 6000
Страница 1: ...ZENER VARIDRIVE SOLUTIONS ZENER SMARTSTART 6000 Soft Starter Instruction Manual...
Страница 2: ......
Страница 49: ...Appendix B Application Diagrams Technical Manual Smartstart 6000 IMI0042 rev K Page 46 General Purpose...
Страница 51: ...Appendix B Application Diagrams Technical Manual Smartstart 6000 IMI0042 rev K Page 48 Irrigation Pump...