Programming
Technical
Manual:
Smartstart
®
6000
IMI0042
rev
K
Page
27
R03
Start
Reset
Activate
or
de
‐
activate
reset
on
a
start
command.
Range:
Enable;
Disable
Default:
Disabled
To
save
changes
To
exit
without
saving
R10
Auto
Restart
R11
AR
Attempts
Enter
number
of
restart
attempts.
Range:
0
‐
15
Default:
0
=
Disabled
To
save
changes
To
exit
without
saving
R12
AR
Min
Delay
Enter
Minimum
delay
before
restart
attempt.
Range:
5
–
3600
seconds
Default:
10
seconds
To
save
changes
To
exit
without
saving
R13
AR
Clear
Time
Enter
time
period
the
soft
starter
must
run
for
to
reset
the
‘R11
AR
attempt
log’
to
0.
Range:
10
–
7200
seconds
Default:
1200
seconds
To
save
changes
To
exit
without
saving
For
more
detailed
description
of
Digital
input
functions
refer
to
table
3
page
33.
X10
DigIn
1
Mode
Activates
digital
input
1.
Range:
Enable;
Invert;
Disable
Default:
Enable
To
save
changes
To
exit
without
saving
X11
DigIn
1
Variable
Set
the
functionality
of
digital
input
1.
Refer
to
page
34
and
page
37
(Brake
On)
for
more
details.
Range:
Trip;
Reset;
Start;
Stop;
Coast;
Local;
ESO;
Brake
On
(see
page
37)
Default:
Reset
To
save
changes
To
exit
without
saving
X12
DigIn
1
Delay
Set
the
delay
that
the
digital
input
needs
to
be
active
for
the
Soft
starter
to
respond.
Range:
0.0
–
300.0
seconds
Default:
0.0
To
save
changes
To
exit
without
saving
X20
DigIn
2
Mode
Activates
digital
input
2.
Range:
Enable;
Invert;
Disable
Default:
Disable
To
save
changes
To
exit
without
saving
X21
DigIn
2
Variable
Set
the
functionality
of
digital
input
2.
Refer
to
page
34
and
page
37
(Brake
On)
for
more
details.
Range:
Trip;
Reset;
Start;
Stop;
Coast;
Local;
ESO;
Brake
On
(see
page
37)
Default:
Trip
To
save
changes
To
exit
without
saving
X22
DigIn
2
Delay
Set
the
delay
that
the
digital
input
needs
to
be
active
for
the
Soft
starter
to
respond.
Range:
0.0
–
300.0
seconds
Default:
‐
To
save
changes
To
exit
without
saving
Y10
Relay
1
Mode
Activates
Relay
1.
Range:
Enable;
Invert;
Disable
Default:
Enable
To
save
changes
To
exit
without
saving
Setup Menu
6 Inputs
Setup Menu
7 Outputs
No.
of
Attempts
AR
Min
Delay
AR
Clear
time
P70 Over Torque
5
10s
1200s
Содержание SMARTSTART 6000
Страница 1: ...ZENER VARIDRIVE SOLUTIONS ZENER SMARTSTART 6000 Soft Starter Instruction Manual...
Страница 2: ......
Страница 49: ...Appendix B Application Diagrams Technical Manual Smartstart 6000 IMI0042 rev K Page 46 General Purpose...
Страница 51: ...Appendix B Application Diagrams Technical Manual Smartstart 6000 IMI0042 rev K Page 48 Irrigation Pump...