Programming
Technical
Manual:
Smartstart
®
6000
IMI0042
rev
K
Page
22
C02
Current
Limit:
The
current
limit
is
expressed
as
a
percentage
of
the
entered
motor
Amps
(FLC).
This
current
limit
setting
operates
during
the
ramp
time
only
and
will
over
‐
ride
the
torque
settings.
Reducing
the
current
limit
will
limit
the
torque
available
to
the
motor
and
load.
If
set
too
low
it
may
prevent
the
motor
from
accelerating
or
reaching
full
speed.
Range:
100
to
450%
FLC
Default:
450%
To
save
changes
To
exit
without
saving
Appendix
A
–
Page
44
provides
a
guide
to
starting
parameters
for
various
load
types.
C03
Current
Limit
2:
(2
nd
Parameter
Enabled)
Current
limit
setting
for
2
nd
parameters
when
enabled
and
activated
used
digital
input
1
or
2.
Range:
100
to
450%
FLC
Default:
450%
To
save
changes
To
exit
without
saving
C10
Accel
Ramp:
To
enter
submenu
to
modify
To
exit
sub
menu
C11
Accel
Time:
Adjust
this
to
vary
the
time
taken
to
ramp
the
voltage
to
full
supply
voltage
or
the
torque
to
reach
the
‘finish
torque’.
The
accel
time
will
affect
the
actual
current
during
starting
–
the
faster
the
rate
of
acceleration
the
higher
the
start
current.
Range:
1
to
60
seconds
Default:
10
s
To
save
changes
To
exit
without
saving
C12
Start
Torque:
The
initial
torque
provided
when
a
start
is
initiated.
Adjust
to
the
lowest
setting
which
allows
the
motor
to
turn
on
a
start
command.
This
is
entered
as
a
percentage
of
nominal
Torque
(FLT).
This
setting
will
be
dependent
on
the
torque
required
by
the
load.
Range:
0%
to
200%
Default:
30%
To
save
changes
To
exit
without
saving
C13
Final
Torque:
(torque
control
only)
This
sets
the
torque
provided
at
the
end
of
the
acceleration
period.
This
is
entered
as
a
percentage
of
nominal
Torque
(FLT).
Range:
15
to
200%
Default:
100%
To
save
changes
To
exit
without
saving
C20
Decel
Ramp:
To
enter
submenu
to
modify
To
exit
sub
menu
C21
Decel
Time:
The
time
taken
to
decelerate
the
motor
from
100%
to
0%
V
or
FLT,
actual
time
dependant
on
torque
settings.
Range:
0
to
120
seconds
Default:
0
s
To
save
changes
To
exit
without
saving
C10 Accel Ramp
10s 30%
100%
Accel
Time
Start
Torque
Final
Torque
DECEL
Time
Release
Torque
C20 Decel Ramp
10s
20%