Installation
‐
Power
Wiring
Technical
Manual:
Smartstart
®
6000
IMI0042
rev
K
Page
6
Power Wiring
The
Zener
Smartstart
®
6000
is
installed
between
the
mains
and
cable
to
the
motor.
If
a
mains
or
isolation
contactor
is
used
it
is
best
controlled
by
the
starters
‘Line
relay’.
3Wire
or
6wire:
The
standard
connection
of
an
electronic
soft
starter
to
a
motor
is
3
wire.
An
alternative
connection
is
6
wire
or
inside
delta
connection.
This
is
commonly
used
when
replacing
a
star/delta
type
motor
starter.
Bypass
/
Continuous:
The
Smartstart
®
6000
can
operate
with
or
without
a
bypass
contactor.
Some
models
include
an
integral
bypass
contactor.
The
bypass
contactor
reduces
the
heat
dissipation
of
the
soft
starter
as
the
semiconductors
are
bypassed
after
the
ramp
time.
Select
cables
&
install
in
compliance
with
local
regulations
Motor
Protection:
The
Smartstart
®
6000
provides
advanced
motor
protection
with
user
selectable
overload
classes,
over
&
under
current
protection,
phase
imbalance
and
thermistor
protection.
It
is
important
that
the
power
wiring
is
followed
correctly
to
ensure
proper
protection
and
starter
performance.
Refer
to
page
23
‐
26
and
39
for
more
details
regarding
motor
protection.
Semiconductor
Fuses
Semiconductor
fuses
are
recommended
for
all
electronic
soft
starters
to
provide
protection
of
the
thyristors
in
the
event
of
an
output
short
circuit.
Semiconductor
fuses
are
strongly
recommended
for
applications
such
as
submersible
pumps.
Semiconductor
fuses
are
optional
with
all
models.
For
smaller
models
(15
–
80Amp)
fuse
kits
are
available.
For
larger
models
semiconductor
fuse
kits
are
available
which
mount
to
the
‘Line’
Busbar.
Refer
to
page
43
for
more
details
on
semi
‐
conductor
fuses.