Relocating the Internal Current
Transformers for 6 wire operation.
The
Smartstart
®
6000
comes
standard
with
internal
Current
Transformers
(C.T’s)
for
monitoring
the
current
during
acceleration,
deceleration
and
when
in
bypass.
It
is
important
that
the
Smartstart
®
6000
be
wired
in
a
manner
to
ensure
the
C.T’s
are
always
monitoring
the
motor
current.
For
this
reason
9
terminals
are
provided.
This
is
important
to
ensure
continual
protection
of
the
soft
starter,
the
motor
and
the
load.
The
correct
installation
of
the
C.T’s
is
crucial
for
optimum
performance
of
the
torque
control
system.
In
6
wire
operation,
it
is
necessary
to
relocate
the
C.T’s
external
to
the
starter.
For
6
wire
operation
the
C.T’s
are
to
be
installed
on
the
incoming
line
supply
cables
so
that
the
line
current
is
monitored
(not
the
phase
currents).
The
Smartstart
®
6000
must
be
purchased
with
C.T’s
external
by
ordering
‘prepared
for
6
wire’;
Part
no.
Description:
TF60015
Prepare
for
6
wire:
6R100
‐
220
TF60016
Prepare
for
6
wire:
6R360
‐
830
NOTE:
6
Wire
using
Internal
CT’s
In
some
cases
the
CT’s
may
remain
internal.
This
is
subject
to
the
Motor
FLC
and
the
Soft
Starter
Rating.
Refer
to
Appendix
E
Page
52
for
more
details.
Installation
of
external
C.T’s
When
relocating
the
C.T’s
external
to
the
soft
starter
it
is
important
to
ensure
the
following:
1.
C.T’s
are
installed
on
L1
&
L3
2.
C.T’s
are
installed
in
correct
direction
P1
label
=
line
side
3.
C.T’s
are
terminated
with
correct
phasing.
S1
=
Red
S2
=
Black
The
C.T’s
supplied
with
the
Smartstart
®
6000
has
a
label
which
shows
the
correct
phase
and
direction.
If
the
C.T’s
are
not
installed
correctly
the
starter
will
display
a
fault
or
a
‘C.T
Phase
error’.
Programming:
Program
the
starter
for
3wire
or
6
wire
operation.
The
selection
available
for
6
wire
is
‘Standard
6
wire’
or
‘alternate
6
wire’,
depending
on
the
wiring
configuration
used.
The
wiring
in
this
manual
is
drawn
for
Standard
6
wire.
Refer
to
page
21:
parameter
‘M04
Motor
Wiring’.
Energise
the
3
Phase
supply
to
the
starter
without
attempting
a
start.
Look
for
a
“W05
MOTOR
WIRING”
warning
and
check
the
“MTR
WIRING
CHK”
is
‘CORRECT’
in
the
diagnostic
menu.
Check
for
correct
installation
The
Correct
CT
connection
can
be
checked
after
the
first
motor
start.
A
CT
phase
error
may
be
identified
under
the
menu
‘Starter
Diagnosis’.
‘+L1
/
+L3’
should
be
displayed.
>
If
L2
is
displayed
move
the
CT
from
L2
phase.
>
If
a
“
‐
“sign
is
displayed,
the
direction
of
the
corresponding
CT
needs
to
be
reversed.
Incorrect
CT
installation
will
result
in
a
“W07
CT
PHASING”
warning
and
affect
the
optimum
starting
of
the
motor.