Control Panel 3 - 7
Bypass Motor OL Indicator
Safeties Open Status Indicator
Drive Fault Indicator
Smoke Purge Status Indicator
Table 3.9 Motor OL Indicator
Indicator Status
Description
On (Red)
The motor overload (S10 on schematic E7L-00) has tripped OFF de-
energizing both the Drive and Bypass Circuits.
Off
The motor overload (S10) is satisfied.
Table 3.10 Safeties Open Indicator
Indicator Status
Description
On (Red)
The NC “motor safety circuit” connected to terminals TB1-1 and TB1-9
has an open circuit condition.
Off
The NC “motor safety circuit” is satisfied or this function is disabled by
DIP switch S2-7.
Table 3.11 Drive Fault Indicator
Indicator Status
Description
On (Red)
The Drive has tripped OFF due to an internal Drive fault.
Off
The Drive is ready for operation, or operating normally.
Table 3.12 Smoke Purge Indicator
Indicator Status
Description
On (Amber)
The Smoke Purge function has been activated, the building fire control
system has closed a contact between terminals TB1-5 and TB1-9.
Off
Smoke Purge is not active, the Drive & Bypass are operating normally.
Содержание E7LBA002
Страница 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Страница 8: ...Introduction vi Notes ...
Страница 12: ...Table of Contents x Notes ...
Страница 54: ...Electrical Installation 2 22 Wiring Diagram ...
Страница 55: ...Electrical Installation 2 23 ...
Страница 87: ...Start Up and Operation 4 9 Notes ...
Страница 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Страница 248: ...Capacity Related Parameters B 6 Notes ...
Страница 279: ...Communications D 27 Note ...
Страница 280: ...Communications D 28 ...
Страница 292: ...Spare Parts F 6 ...
Страница 304: ...Index 12 ...
Страница 305: ......