Programming 5 - 40
As shown in Table 5.8, it is possible to use analog inputs in place of Frequency Reference 1 and Frequency
Reference 2.
If b1-01= “1: Terminals” then the analog input A1 will be used instead of Frequency Reference 1 for the first preset speed.
If b1-01= “0: Operator”, then Frequency Reference 1 will be used.
If H3-09= “2: Aux Reference” then the analog input A2 will be used instead of Frequency Reference 2 for the second
preset speed. If H3-09
≠
2 then Frequency Reference 2 will be used.
IMPORTANT
The programming of d1-01 through d1-04 and d1-17 will be affected by the setting of o1-03. The programming
of these parameters will be in the units specified by Display Scaling parameter (o1-03).