Parameters A - 11
Motor Setup
E2-01
Motor Rated Current
Motor Rated FLA
Set to the motor nameplate full load amps.
10% to
200%
kVA
Dependent
Quick Setting
E2-03
No-Load Current
Sets the magnetizing current of the motor.
kVA
Dependent
kVA
Dependent
Programming
E2-05
Motor Line-to-Line
Resistance
Term Resistance
Phase to phase motor resistance, normally set by the autotuning
routine.
0.000 to
65.000
kVA
Dependent
Programming
Com OPT Setup
F6-01
Operation Selection after
Communication Error
Comm Bus Flt Sel
Sets the stopping method for option PCB communications error
(BUS fault). Active only when a communications option PCB is
installed and when b1-01 or b1-02 = 3.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0 to 3
1
Programming
F6-02
Detection Selection of Exter-
nal Fault from Communica-
tion Option Card
EF0 Detection
0: Always detected
1: Detected only during run
0 or 1
0
Programming
F6-03
Stopping Method for
External Fault from
Communication Option Card
EF0 Fault Action
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0 to 3
1
Programming
F6-05
Current Monitor Display Unit
Selection
Current Unit Sel
0: A Display (Amps Display)
1: 100%/8192 (Drive Rated Current)
0 or 1
0
Programming
Table A.1 Parameter List (Continued)
Parameter
No.
Parameter Name
LCD Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Содержание E7LBA002
Страница 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Страница 8: ...Introduction vi Notes ...
Страница 12: ...Table of Contents x Notes ...
Страница 54: ...Electrical Installation 2 22 Wiring Diagram ...
Страница 55: ...Electrical Installation 2 23 ...
Страница 87: ...Start Up and Operation 4 9 Notes ...
Страница 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Страница 248: ...Capacity Related Parameters B 6 Notes ...
Страница 279: ...Communications D 27 Note ...
Страница 280: ...Communications D 28 ...
Страница 292: ...Spare Parts F 6 ...
Страница 304: ...Index 12 ...
Страница 305: ......