Programming 5 - 46
E1-05 Maximum Output Voltage
Setting Range:
0.0 to 255.0V (208V/240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 208.0V (208V Models)
230.0V (240V Models)
460.0V (480V Models)
E1-06 Base Frequency
Setting Range:
0.0 to 200.0 Hz (settings above 120.0 Hz are currently not supported)
Factory Default: 60.0 Hz
E1-07 Mid Output Frequency A
Setting Range:
0.0 to 200.0 Hz (settings above 120.0 Hz are currently not supported)
Factory Default: 3.0 Hz
E1-08 Mid Output Voltage A
Setting Range:
0.0 to 255.0V (208V/240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 18.0V (208V Models)
18.0V (240V Models)
33.6V (480V Models)
E1-09 Minimum Output Frequency
Setting Range:
0.0 to 200.0 Hz (settings above 120.0 Hz are currently not supported)
Factory Default: 1.5 Hz
E1-10 Mid Output Voltage
Setting Range:
0.0 to 255.0V (208V/240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 10.8V (208V Models)
10.8V (240V Models)
16.8V (480V Models)
E1-11 Mid Output Frequency B
Setting Range:
0.0 to 200.0 Hz (settings above 120.0 Hz are currently not supported)
Factory Default: 0.0 Hz
E1-12 Mid Output Voltage B
E1-13 Base Voltage
Setting Range:
0.0 to 255.0V (208V/240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 0.0V (208V Models)
0.0V (240V Models)
0.0V (480V Models)
Содержание E7LBA002
Страница 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Страница 8: ...Introduction vi Notes ...
Страница 12: ...Table of Contents x Notes ...
Страница 54: ...Electrical Installation 2 22 Wiring Diagram ...
Страница 55: ...Electrical Installation 2 23 ...
Страница 87: ...Start Up and Operation 4 9 Notes ...
Страница 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Страница 248: ...Capacity Related Parameters B 6 Notes ...
Страница 279: ...Communications D 27 Note ...
Страница 280: ...Communications D 28 ...
Страница 292: ...Spare Parts F 6 ...
Страница 304: ...Index 12 ...
Страница 305: ......