Parameters A - 5
b2-09
Motor Pre-Heat Current
Preheat Current
Motor Pre-heat current in % of drive rated current. This is used to
keep the motor warm to prevent condensation and is used in
conjunction with a digital input (data = 60).
0 to100
0%
Programming
b2-10
Motor Pre-Heat Current 2
Preheat Current2
Sets the DC preheat current for multi-function output setting 80
(Motor Preheat 2) as a percentage of Motor Rated Current (E2-01).
0 to 10%
5
Programming
Speed Search
b3-01
Speed Search Selection
SpdSrch at Start
Enables/disables and selects the speed search function at start.
0: SpdsrchF Disable - Speed search at start is disabled
(estimated speed method is used at other times)
1: SpdsrchF Enable - Speed search is enabled
(estimated speed method)
2: SpdsrchI Disable - Speed search at start is disabled
(current detection method is used at other times)
3: SpdscrhI Enable - Speed search is enabled
(current detection method)
Estimated Speed Method:
Actual motor speed and direction is estimated, then the motor is
ramped from that speed to the commanded speed.
Current Detection Method:
Current level is monitored while output frequency is ramped down.
0 to 3
2
Programming
b3-02
Speed Search Deactivation
Current
SpdSrch Current
Used only when b3-01 = 3. Sets the speed search operation current
as a percentage of drive rated current.
0 to 200
120%
Programming
b3-03
Speed Search Deceleration
Time
SpdSrch Dec Time
Used only when b3-01 = 3. Sets the deceleration time during speed
search.
0.1 to 10.0
2.0sec
Programming
b3-05
Speed Search Delay Time
Search Delay
Delays the speed search operation after a momentary power loss to
allow time for an external output contactor to re-energize.
0.0 to
20.0sec
0.2sec
Programming
b3-14
Bidirectional Speed Search
Selection
Bidir Search Sel
0: Disabled
1: Enabled
0 or 1
1
Programming
Delay Timers
b4-01
Timer Function ON-Delay
Time
Delay-ON Timer
Used in conjunction with a multi-function digital input and a
multi-function digital output. This sets the amount of time between
when the digital input is closed, and the digital output is energized.
0.0 to
3000.0
0.0sec
Programming
b4-02
Timer Function OFF-Delay
Time
Delay-OFF Timer
Used in conjunction with a multi-function digital input and a
multi-function digital output. This sets the amount of time the
output stays energized after the digital input is opened.
0.0 to
3000.0
0.0sec
Programming
PI Control
b5-01
PI Mode Setting
PI Mode
This parameter enables / disables the closed loop (PI) controller.
0: Disabled
1: Enabled (commanded speed becomes PI setpoint)
3: Fref+PI
0, 1, 3
0
Quick Setting
b5-02
Proportional Gain Setting
P Gain
Sets the proportional gain of the PI controller.
0.00 to
25.00
2.00
Quick Setting*
b5-03
Integral Time Setting
PI I Time
Sets the integral time for the PI controller. A setting of zero
disables integral control.
0.0 to 360.0
5.0sec
Quick Setting*
b5-04
Integral Limit Setting
PI I Limit
Sets the maximum output possible from the integrator. Set as a %
of fmax.
0.0 to
100.0
100%
Programming
b5-06
PI Output Limit
PI Limit
Sets the maximum output possible from the entire PI controller.
Set as a % of fmax.
0.00 to
100.0
100.0%
Programming
b5-07
PI Offset Adjustment
PI Offset
Sets the amount of offset of the output of the PI controller. Set as a
% of fmax.
The PI Offset Adjustment parameter has two different uses.
Parameter b5-07 serves different functions depending on whether it
is used on a standard PI loop or a Differential PI loop.
1: Parameter b5-07 causes an offset to be applied to the output of
the PI function in a non-Differential PI loop. Every time the PI
output is updated, the offset is summed with the PI output. This
can be used to artificially kick-start a slow starting PI loop.
2: If the Drive is configured for Differential PI Regulation
(H3-09=16), then the PI Offset is the targeted maintained differ-
ential between the signal measured on analog input A1 and the
signal measured on analog input A2.
–100.0 to
+100.0
0.0%
Programming
Denotes that parameter can be changed when the drive is running.
* Menu location is Quick Setting when b5-01=1, and Programming when b5-01=0.
Table A.1 Parameter List (Continued)
Parameter
No.
Parameter Name
LCD Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Содержание E7LBA002
Страница 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Страница 8: ...Introduction vi Notes ...
Страница 12: ...Table of Contents x Notes ...
Страница 54: ...Electrical Installation 2 22 Wiring Diagram ...
Страница 55: ...Electrical Installation 2 23 ...
Страница 87: ...Start Up and Operation 4 9 Notes ...
Страница 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Страница 248: ...Capacity Related Parameters B 6 Notes ...
Страница 279: ...Communications D 27 Note ...
Страница 280: ...Communications D 28 ...
Страница 292: ...Spare Parts F 6 ...
Страница 304: ...Index 12 ...
Страница 305: ......