Programming 5 - 52
To switch the command source between the serial communication port and the control circuit terminals be sure to program the
following parameters:
•
Set b1-01 (Frequency Reference Selection) to 1 (Terminals).
•
Set b1-02 (Run Command Selection) to 1 (Terminals).
•
Set H1-0x (Input Terminal Function Selection) to 6B or 6C.
The Com/Inv Sel 2 function will operate the same way except the logic is reversed. When a digital input is programmed for the
Com/Inv Selection function (H1-0x= 6C) that input will function as follows:
Table 5.12
Option/Inv Function Input Status
Run and Speed Command Source
OPEN
From the control circuit and analog input terminals
CLOSED
From Serial Com port (R+,R-,S+, and S-) (embedded protocols)
Table 5.13
Option/Inv Function Input Status
Run and Speed Command Source
OPEN
From Serial Com port (R+, R-, S+, and S-) (embedded protocols)
CLOSED
From the control circuit and analog input terminals
IMPORTANT
Switching the Reference and Run sources can only be done while the Drive is stopped.
Содержание E7LBA002
Страница 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Страница 8: ...Introduction vi Notes ...
Страница 12: ...Table of Contents x Notes ...
Страница 54: ...Electrical Installation 2 22 Wiring Diagram ...
Страница 55: ...Electrical Installation 2 23 ...
Страница 87: ...Start Up and Operation 4 9 Notes ...
Страница 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Страница 248: ...Capacity Related Parameters B 6 Notes ...
Страница 279: ...Communications D 27 Note ...
Страница 280: ...Communications D 28 ...
Страница 292: ...Spare Parts F 6 ...
Страница 304: ...Index 12 ...
Страница 305: ......