Diagnostic & Troubleshooting 6 - 20
If the Motor Does Not Operate
Use the following information if the motor does not operate.
Ensure the digital operator is securely connected to the Drive.
The motor does not operate when the HAND key on the Digital Operator is pressed.
The following causes are possible:
The Speed Command (Frequency Reference) is too low.
If the Speed Command (frequency reference) is set below the frequency set in E1-09 (Minimum Output Frequency), the Drive
will not operate.
Raise the Speed Command to at least the minimum output frequency.
The motor does not operate when an external run command is input.
The following causes are possible.
The Drive is not in Drive mode.
If the Drive is not in Drive mode, it will remain in ready status and will not start. Press the MENU key once and press the
DATA/ENTER key. The Drive is now in Drive mode.
The Speed Command is too low.
If the Speed Command is set below the frequency set in E1-09 (Minimum Output Frequency), the Drive will not operate.
Raise the Speed Command to at least the minimum output frequency.
Содержание E7LBA002
Страница 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Страница 8: ...Introduction vi Notes ...
Страница 12: ...Table of Contents x Notes ...
Страница 54: ...Electrical Installation 2 22 Wiring Diagram ...
Страница 55: ...Electrical Installation 2 23 ...
Страница 87: ...Start Up and Operation 4 9 Notes ...
Страница 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Страница 248: ...Capacity Related Parameters B 6 Notes ...
Страница 279: ...Communications D 27 Note ...
Страница 280: ...Communications D 28 ...
Страница 292: ...Spare Parts F 6 ...
Страница 304: ...Index 12 ...
Страница 305: ......