Programming 5 - 50
The Drive has five multi-function contact digital inputs. By programming parameters H1-01 through H1-05, the user can assign
specific functions to each input. Below is a table with a complete list of all of the digital input functions. The programming
manual has a more detailed description of each of the functions.
Following are descriptions of only those parameters that are required for Bypass operations and PI control.
Function: Multi-step Ref 1
Setting: 3
Function: Multi-step Ref 2
Setting: 4
The Drive can be programmed to step through four preset speeds and a jog. It is also possible to mix in the analog inputs as
speed references that can be chosen in place of the first and second preset frequency references. The selection of which preset
speed will be the active speed command is determined by the status of the digital inputs set for Multi-step Ref 1 (H1-0x= 3)
and Multi-step Ref 2 (H1-0x= 4). Changing the active speed command via the Multi-step References can be done while the
Drive is running.
Table 5.10 Digital Input Functions
Parameter
setting
Function
Parameter
setting
Function
0
3-Wire Control
1C
Trim Control Increase
1
Local/Remote Selection
1D
Trim Control Decrease
2
Option/Inv Selection 1
1E
Reference Sample Hold
3
Multi-step Reference 1
20-2F
External Fault
4
Multi-step Reference 2
30
Integral Reset
6
Jog Frequency Reference 1
31
Integral Hold
7
Multi-Accel/Decel 1
34
PI Soft Start Cancel
8
External Baseblock N.O.
35
PI Input Characteristic
9
External Baseblock N.C.
36
Option/Inv Selection 2
A
Accel/Decel Ramp Hold
60
Motor Pre-heat
C
Terminal A2 Enable
61
Speed Search 1
F
Terminal Not Used
62
Speed Search 2
10
MOP Increase
64
Speed Search 3
11
MOP Decrease
67
Communications Test Mode
12
Forward Jog
68
High Slip Braking
13
Reverse Jog
69
Jog Frequency Reference 2
14
Fault Reset
6A
Drive Enable (Cycle Run)
15
Fast Stop N.O.
6B
Com/Inv Selection
17
Fast Stop N.C.
6C
Com/Inv SEL 2
18
Timer Function
6D
Auto Mode @ Close
19
PI Disable
6E
Hand Mode @ Close
1B
Program Lockout
70
Drive Enable (Accept Run)
Содержание E7LBA002
Страница 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Страница 8: ...Introduction vi Notes ...
Страница 12: ...Table of Contents x Notes ...
Страница 54: ...Electrical Installation 2 22 Wiring Diagram ...
Страница 55: ...Electrical Installation 2 23 ...
Страница 87: ...Start Up and Operation 4 9 Notes ...
Страница 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Страница 248: ...Capacity Related Parameters B 6 Notes ...
Страница 279: ...Communications D 27 Note ...
Страница 280: ...Communications D 28 ...
Страница 292: ...Spare Parts F 6 ...
Страница 304: ...Index 12 ...