Programming 5 - 49
F6-05 Current Scaling via Communication Option PCB
A communication option card can read the Drive’s DPRAM to access the current monitor. The format of the current reading in
the DPRAM will be determined by parameter F6-05.
F6-05= “0: A Display”
Current is a decimal number corresponding to actual Amperes
F6-05= “1: 100%/8192 (Drive Rated Current)”
Current reading is a number where
8192 = 100% of Drive rated output current
H1 Digital Inputs
H1-01 Drive Terminal S3 Function Selection
H1-02 Drive Terminal S4 Function Selection
H1-03 Drive Terminal S5 Function Selection
H1-04 Drive Terminal S6 Function Selection
H1-05 Drive Terminal S7 Function Selection
Setting Range:
0 to 6E
Factory Default: H1-01= “70: Bypass Drv Envl” This is one of the special parameter settings required by the Bypass logic
circuit. See Table 5.1.
H1-02= This is one of the special parameter settings required by the Bypass logic circuit. See Table 5.2
H1-03= This is one of the special parameter settings required by the Bypass logic circuit. See Table 5.2.
H1-04= “4: Multi-Step Ref 2” (2 Wire)
“3: Multi-Step Ref 1” (3 Wire)
H1-05= “6: Jog Freq Ref ” (2 Wire)
“4: Multi-Step Ref 2” (3 Wire)
Setting
Description
0
A Display (
factory default
)
1
100%/8192 (Drive Rated Current)
Содержание E7LBA002
Страница 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Страница 8: ...Introduction vi Notes ...
Страница 12: ...Table of Contents x Notes ...
Страница 54: ...Electrical Installation 2 22 Wiring Diagram ...
Страница 55: ...Electrical Installation 2 23 ...
Страница 87: ...Start Up and Operation 4 9 Notes ...
Страница 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Страница 248: ...Capacity Related Parameters B 6 Notes ...
Страница 279: ...Communications D 27 Note ...
Страница 280: ...Communications D 28 ...
Страница 292: ...Spare Parts F 6 ...
Страница 304: ...Index 12 ...
Страница 305: ......