Programming 5 - 53
H2 Digital Outputs
H2-01 Drive Terminal M1-M2 Function Selection
H2-02 Drive Terminal M3-M4 Function Selection
Setting Range:
0 to 3B
Factory Default: H2-01= “0: During Run 1”
H2-02= “3B: Run Src Com/Opt”
H2-01 and H2-02 are two of the special parameter settings required by the Bypass logic circuit. See Table 5.1.
The Drive has two multi-function outputs. By programming parameters H2-01 and H2-02, the user can assign specific
functions to each output. Below is a table with a complete list of all of the digital output functions. Refer to the Programming
Manual for a more detailed description of each of the functions.
Table 5.14 Digital Output Functions
Parameter
setting
Function
Parameter
Setting
Function
0
During Run1
F
Terminal Not Used
1
Zero Speed
10
Minor Fault
2
F
REF
/F
OUT
Agree 1
11
Reset Cmd Active
3
F
REF
/Set Agree 1
12
Timer Output
4
Frequency Detect 1
17
Torque Detect 1 N.C.
5
Frequency Detect 2
1A
Reverse Direction
6
Drive Ready
1E
Restart Enabled
7
DC Bus Undervoltage
1F
Overload (OL1)
8
Baseblock 1
20
OH Pre-alarm
9
Option Reference
38
Drive Enable
A
Remote Operation
39
Drive Waiting
B
Torque Detect 1 N.O.
3A
Frequency Reduced, OH
C
Loss of Reference
3B
Run from Serial Com
E
Fault
Содержание E7LBA002
Страница 1: ...E7L Drive Bypass Technical Manual Model E7L Document Number TM E7L 01 ...
Страница 8: ...Introduction vi Notes ...
Страница 12: ...Table of Contents x Notes ...
Страница 54: ...Electrical Installation 2 22 Wiring Diagram ...
Страница 55: ...Electrical Installation 2 23 ...
Страница 87: ...Start Up and Operation 4 9 Notes ...
Страница 202: ...Diagnostic Troubleshooting 6 30 Notes ...
Страница 248: ...Capacity Related Parameters B 6 Notes ...
Страница 279: ...Communications D 27 Note ...
Страница 280: ...Communications D 28 ...
Страница 292: ...Spare Parts F 6 ...
Страница 304: ...Index 12 ...
Страница 305: ......