Faults, causes and remedies
en
Installation and operating instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
255
Code
Warning
Cause
Remedy
Additional information
about causes and rem-
edy:
Twin-head pump func-
tion is only possible with
two compatible pumps
of the same type.
586
Overvoltage
Power supply is too
high.
Check power supply
Additional information
about causes and rem-
edy:
The pump is running. If
the voltage continues to
increase, the pump is
shut down.
Excessive voltages can
damage the pump.
587
Battery weak.
Battery power too
low
Replace battery.
Additional information
about causes and rem-
edies:
If the battery power is
high enough, the time
information, e.g. in heat
measurement and stat-
istics, is displayed cor-
rectly.
If the battery power is
too low, it may not be
possible to maintain
time recording.
This does not impair the
pump function
590
MFA
1)
partner type is not
appropriate.
A MFA
1)
partner does
not have the appro-
priate type.
Check type and software
of the partner pump.
Additional information
about causes and rem-
edy:
A maximum replace-
ment flow is provided
for the Multi-Flow Ad-
aptation partner.
Check the partners
highlighted with (!) in
the MFA
1)
overview of
the context menu.
1)
MFA = Multi-Flow Adaptation
2)
BMS = Building Management System
18.5
Configuration warnings
Configuration warnings occur if an incomplete or contradictory configuration has been
made.
Example:
The “Hall temperature control” function requires a temperature sensor. The corre-
sponding source is not specified or not correctly configured.
Содержание Stratos GIGA2.0-D
Страница 2: ...Fig I Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 D...
Страница 3: ...Fig II Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 E E D...
Страница 4: ...Fig III Stratos GIGA2 0 I Stratos GIGA2 0 D DN 100 DN 125 D D E...
Страница 5: ...5 Deutsch 6 English 139 Fran ais 270 Nederlands 409...
Страница 548: ......
Страница 549: ......
Страница 550: ......
Страница 551: ......