Communication interfaces: Setting and function
en
Installation and operating instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
217
Selection option
Function control input DI1 or DI2
Heating/cooling switchover
3)
Contact open:
“Heating” active.
Contact closed:
“Cooling” active.
Table 38:
Function control input DI1 or DI2
1)
Function: see “Settings menu – Manual operation” [
208] section.
2)
3)
To guarantee the heating/cooling switchover function operates correctly at the digital
input:
1.
go to
“Settings” menu, “Set control mode”, “Setting assistant” and select the
“Heating & cooling” application
and
2.
go to
“Settings” menu, “Set control mode”, “Heating/cooling switchover” and
select the “Binary input” option as switchover criterion.
Procedure with EXT. OFF for twin-head pumps
The function EXT. OFF always behaves as follows:
ƒ
EXT. OFF active: contact is open, pump is stopped (OFF).
ƒ
EXT. OFF inactive: contact is closed, pump runs in normal operation (ON).
ƒ
Main pump: twin-head pump partner with connected differential pressure sensor
ƒ
Partner pump: twin-head pump partner without connected differential pressure
sensor
The configuration of the control inputs has three possible modes for EXT. OFF which
can influence the behaviour of the two twin-head pump partners.
“External OFF” twin-head pump
The control input
of this pump head
switches the whole
twin-head pump off.
The control input of the
partner pump switches
the partner pump off.
Single mode
Combined mode
System mode
Fig. 65:
Selectable modes for EXT. OFF for twin-head pumps
System mode
The control input of the main pump is occupied with a control cable and configured to
EXT. OFF.
The control input on the
main pump switches both twin-head pump partners
.
The
control input of the partner pump
is ignored and
has
no significance
regardless of
its configuration. If the main pump malfunctions or if the twin-head pump connection
is disconnected, the partner pump is also stopped.
Main pump
Partner pump
States
EXT.
OFF
Behaviour
of the
pump mo-
tor
Display
text for
active in-
fluences
EXT.
OFF
Behaviour
of the
pump mo-
tor
Display
text for
active in-
fluences
1
Active
Off
OFF
Override
OFF (DI1/2)
Active
Off
OFF
Override
OFF (DI1/2)
Содержание Stratos GIGA2.0-D
Страница 2: ...Fig I Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 D...
Страница 3: ...Fig II Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 E E D...
Страница 4: ...Fig III Stratos GIGA2 0 I Stratos GIGA2 0 D DN 100 DN 125 D D E...
Страница 5: ...5 Deutsch 6 English 139 Fran ais 270 Nederlands 409...
Страница 548: ......
Страница 549: ......
Страница 550: ......
Страница 551: ......