Communication interfaces: Setting and function
226
WILO SE 2021-12
Use standard values
Analogue input (AI2)
Set the signal/values
assignment.
User-defined settings
Specifications
Fig. 75:
Use standard values
Defined standards for the transfer of the signal are used with “Use specifications”. Fi-
nally the setting of the analogue input is ended as setpoint sensor.
OFF:
1.0 V
ON:
2.0
Min:
3.0 V
Max:
10.0 V
Table 50:
Standard signal assignment
With the selection of “User-defined settings”, additional settings must be made:
For the signal types “0 ... 10 V” and “0 ... 20 mA”, a cable break detection with a para-
meterisable threshold can be optionally activated.
Optional cable break detection
Analogue input (AI2)
Signal strength below
the set limit value
is interpreted as
a cable break.
Switched on
Switched off
Fig. 76:
Optional cable break detection
Select “Switched off” to switch off cable break detection.
Select “Switched on” to activate cable break detection only within an adjustable limit
value.