Communication interfaces: Setting and function
en
Installation and operating instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
223
Setpoint source
Qu
Setpoint comes from
analogue input (AI2)
Analogue input 2
Analogue input 3
Analogue input 4
CIF module
Analogue input 1
Fig. 70:
Setpoint source
NOTICE
When an analogue input is selected as setpoint source, but the type of use for ex-
ample has been selected as “Not configured” or as actual value input, the pump dis-
plays a configuration warning.
The deviation type is accepted as setpoint.
Either another source must be selected or the source must be configured as setpoint
source.
NOTICE
After selecting one of the external sources, the setpoint is paired to this external
source and can no longer be adjusted in the setpoint editor or on the home screen.
This pairing can only be cancelled in the context menu of the setpoint editor (as de-
scribed above) or in the “External setpoint sensor” menu. The setpoint source must
be adjusted again to “Internal setpoint”.
The pairing between external source and setpoint is marked both in the
home
screen, and in the setpoint editor in
blue
. The status LED also becomes blue.
After selecting one of the external sources, the “External setpoint source” menu is
available to configure the parameters of the external source.
For this purpose, go to the
“Settings” menu and select:
1.
“Set control mode”
2.
“External setpoint source”
Содержание Stratos GIGA2.0-D
Страница 2: ...Fig I Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 D...
Страница 3: ...Fig II Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 E E D...
Страница 4: ...Fig III Stratos GIGA2 0 I Stratos GIGA2 0 D DN 100 DN 125 D D E...
Страница 5: ...5 Deutsch 6 English 139 Fran ais 270 Nederlands 409...
Страница 548: ......
Страница 549: ......
Страница 550: ......
Страница 551: ......