Faults, causes and remedies
256
WILO SE 2021-12
Code
Fault
Cause
Remedy
601
Setpoint source not
suitably configured.
Setpoint is not con-
nected to correct
source. Input is not
correctly configured.
Configure source or
select another source.
The setpoint source is not correctly configured. In the context menu there is
a link for configuring the setpoint source.
602
Setpoint source not
available.
Setpoint not connec-
ted to existing CIF
module.
Insert CIF module.
Activate CIF module.
The setpoint source or the CIF module is not correctly configured. In the con-
text menu there are links for configuration.
603
Sensor source not suit-
ably configured.
Sensor 1 is not con-
nected to correct
source. Input is not
correctly configured.
Configure source.
Select other source.
The sensor source is not correctly configured. In the context menu there is a
link for configuring the sensor source.
604
Same sensor source not
possible.
Sensor sources are
configured to the
same source.
Configure a sensor source
to another source.
The sensor sources are not correctly configured. In the context menu there is
a link for configuring the sensor sources.
606
Sensor source not avail-
able.
Sensor value 1 is not
connected to existing
CIF module.
Insert CIF module.
Activate CIF module.
The sensor source or the CIF module is not correctly configured. In the con-
text menu there are links for configuration.
607
Sensor source not suit-
ably configured.
Sensor 2 is not con-
nected to correct
source. Input is not
correctly configured.
Configure source or
select another source.
The sensor source is not correctly configured. In the context menu there is a
link for configuring the sensor source.
609
Sensor source not avail-
able.
Sensor value 2 is not
connected to existing
CIF module.
Insert CIF module.
Activate CIF module.
The sensor source or the CIF module is not correctly configured. In the con-
text menu there are links for configuration.
610
Sensor source not suit-
ably configured.
Feed temperature
sensor is not connec-
ted to correct source.
Input is not correctly
configured.
Configure source to “tem-
perature sensor” usage
type or select another
source.
The sensor source is not correctly configured. In the context menu there is a
link for configuring the sensor source.
611
Same sensor source not
possible.
Sensor sources for
heat meter con-
figured for the same
source.
Configure one of the
sensor sources for the heat
meter to another source.
The sensor sources are not correctly configured. In the context menu there is
a link for configuring the sensor sources.
614
Sensor source not avail-
able.
Feed temperature is
not connected to ex-
isting CIF module.
Insert CIF module.
Activate CIF module.
The sensor source or the CIF module is not correctly configured. In the con-
text menu there are links for configuration.
Содержание Stratos GIGA2.0-D
Страница 2: ...Fig I Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 D...
Страница 3: ...Fig II Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 E E D...
Страница 4: ...Fig III Stratos GIGA2 0 I Stratos GIGA2 0 D DN 100 DN 125 D D E...
Страница 5: ...5 Deutsch 6 English 139 Fran ais 270 Nederlands 409...
Страница 548: ......
Страница 549: ......
Страница 550: ......
Страница 551: ......