en
Commissioning
180
WILO SE 2021-12
ƒ
Turn
: menu selection and parameter setting.
ƒ
Press
: activation of menus or confirming settings.
Press the “Back” button
(“Description of operating elements” [
change the focus back to the previous focus. Consequently, the focus moves one level
further up in the structure or to a previous setting.
Pressing the “Back” button
after having changed a setting (yellow focus) without
confirming the changed value returns the focus to the previous focus. The adjusted
value will be discarded. The previous value remains unchanged.
If the “Back” button
is pressed for more than 2 seconds, the “Home screen” opens
and the pump can be operated from the main menu.
NOTICE
If there are no warning or error messages, the display on the electronic module will
switch off 2 minutes after the last time it was operated.
• If the operating button is pressed or turned again within 7 minutes, the previously
exited menu will appear. You can continue to configure settings.
• If the operating button is not pressed or turned for more than 7 minutes, any un-
confirmed settings will be lost. Pressing the button again opens the Home screen on
the display and the pump can be operated from the main menu.
10.3.3
Initial settings menu
The settings menu will appear in the display during initial commissioning of the pump.
NOTICE
The factory setting for variant ... R1 (without differential pressure sensor as de-
livered) is the basic control mode “Constant speed”. The factory setting mentioned
below refers to the variant with a differential pressure sensor fitted in the factory.
Start with factory settings
Pump operates for radiator
First settings
for commissioning
Application:
Radiator
Control mode:
Dynamic Adapt plus
The pump has been
successfully installed.
Pump is currently running in
factory setting:
WELCOME - WILO-STRATOS GIGA2.0
Fig. 31:
Initial settings menu
ƒ
You can exit the initial settings menu by activating “Start with factory settings”
menu. The display changes to the main menu. The pump continues to run using the
factory settings.
ƒ
In the “Initial settings” menu, language, units and applications can be selected and
adjusted. The chosen initial settings are confirmed by activating “Finish initial set-
tings”. The display changes to the main menu.
10.3.4
Main menu
Quit the Initial settings menu to open the Home screen on the display and operate it
from the main menu.
Содержание Stratos GIGA2.0-D
Страница 2: ...Fig I Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 D...
Страница 3: ...Fig II Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 E E D...
Страница 4: ...Fig III Stratos GIGA2 0 I Stratos GIGA2 0 D DN 100 DN 125 D D E...
Страница 5: ...5 Deutsch 6 English 139 Fran ais 270 Nederlands 409...
Страница 548: ......
Страница 549: ......
Страница 550: ......
Страница 551: ......