en
Setting the control functions
194
WILO SE 2021-12
System types for heating application
Control mode
‣ Underfloor heating
‣ Ceiling heating
Differential pressure Δp-c
Dynamic Adapt plus
Hall temperature T-const
‣ Fan heater
Differential pressure Δp-v
Dynamic Adapt plus
Hall temperature T-const.
‣ Concrete core heating
Differential pressure Δp-c
Dynamic Adapt plus
Feed/return ΔT
Volume flow cQ
‣ Hydraulic shunt
Sec. feed temperature T-const.
Return ΔT
Multi-Flow Adaptation
Volume flow cQ
‣ Differential pressure-less distributor
‣ Buffer heating
Multi-Flow Adaptation
Volume flow cQ
‣ Heat exchanger
Sec. feed temperature T-const.
Feed ΔT
Multi-Flow Adaptation
Volume flow cQ
‣ Heat source circuit
(heat pump)
Feed/return ΔT
Volume flow cQ
‣ District heating circuit
Differential pressure Δp-c
Differential pressure Δp-v
Index circuit Δp-c
‣ Basic control modes
Differential pressure Δp-c
Differential pressure Δp-v
Index circuit Δp-c
Dynamic Adapt plus
Volume flow cQ
Temperature T-const
Temperature ΔT-const.
Speed n-const.
Table 22:
Selection system type and control mode for “Heating” application
After having selected the desired system type and control mode for the “Heating” ap-
plication, select the control mode for the “Cooling” application.
System types for cooling application
Control mode
‣ Ceiling cooling
‣ Underfloor cooling
Differential pressure Δp-c
Dynamic Adapt plus
Hall temperature T-const
‣ Air-conditioning device
Differential pressure Δp-v
Dynamic Adapt plus
Hall temperature T-const.
‣ Concrete core cooling
Differential pressure Δp-c
Dynamic Adapt plus
Feed/return ΔT
Volume flow cQ
Содержание Stratos GIGA2.0-D
Страница 2: ...Fig I Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 D...
Страница 3: ...Fig II Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 E E D...
Страница 4: ...Fig III Stratos GIGA2 0 I Stratos GIGA2 0 D DN 100 DN 125 D D E...
Страница 5: ...5 Deutsch 6 English 139 Fran ais 270 Nederlands 409...
Страница 548: ......
Страница 549: ......
Страница 550: ......
Страница 551: ......